GE Multilin
T60 Transformer Protection System
5-25
5 SETTINGS
5.2 PRODUCT SETUP
5
The
GSSE ID
setting represents the IEC 61850 GSSE application ID name string sent as part of each GSSE message. This
string identifies the GSSE message to the receiving device. In T60 releases previous to 5.0x, this name string was repre-
sented by the
RELAY NAME
setting.
The fixed GOOSE settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
TRANSMISSION
FIXED GOOSE
These settings are applicable to fixed (DNA/UserSt) GOOSE only.
The
GOOSE ID
setting represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each GOOSE
message. This string identifies the GOOSE message to the receiving device. In revisions previous to 5.0x, this name string
was represented by the
RELAY NAME
setting.
The
DESTINATION MAC
setting allows the destination Ethernet MAC address to be set. This address must be a multicast
address; the least significant bit of the first byte must be set. In T60 releases previous to 5.0x, the destination Ethernet MAC
address was determined automatically by taking the sending MAC address (that is, the unique, local MAC address of the
T60) and setting the multicast bit.
The
GOOSE VLAN PRIORITY
setting indicates the Ethernet priority of GOOSE messages. This allows GOOSE messages to
have higher priority than other Ethernet data. The
GOOSE ETYPE APPID
setting allows the selection of a specific application
ID for each GOOSE sending device. This value can be left at its default if the feature is not required. Both the
GOOSE VLAN
PRIORITY
and
GOOSE ETYPE APPID
settings are required by IEC 61850.
FIXED GOOSE
GOOSE FUNCTION:
Disabled
Range: Enabled, Disabled
MESSAGE
GOOSE ID:
GOOSEOut
Range: 65-character ASCII string
MESSAGE
DESTINATION MAC:
000000000000
Range: standard MAC address
MESSAGE
GOOSE VLAN PRIORITY:
4
Range: 0 to 7 in steps of 1
MESSAGE
GOOSE VLAN ID:
0
Range: 0 to 4095 in steps of 1
MESSAGE
GOOSE ETYPE APPID:
0
Range: 0 to 16383 in steps of 1
Summary of Contents for UR T60
Page 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...