5-180
T60 Transformer Protection System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
f) LOSS OF LIFE
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
TRANSFORMER
LOSS OF LIFE
The Loss of Life element detects the accumulated total consumed transformer life. This element can be set to issue an
alarm or trip when the actual accumulated transformer life becomes larger than the user-specified loss of life pickup value.
For new transformers installations, the
XFMR INITIAL LOSS OF LIFE
setting should be “0”. For previously installed transform-
ers, the user should pre-determine the consumed transformer life in hours.
•
LOSS OF LIFE INITIAL VALUE
: Enter a setting for the consumed transformer life in hours. When the Loss of Life ele-
ment is enabled, the computed loss of life will be added to the initial loss of life.
•
LOSS OF LIFE PICKUP
: Enter the expended life, in hours, required for operation of the element. This setting should
be above the total transformer life set as a reference based on nominal loading conditions and a 30°C ambient temper-
ature, as outlined in the IEEE standards.
Figure 5–94: TRANSFORMER LOSS OF LIFE LOGIC
LOSS OF LIFE
LOSS OF LIFE
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
LOSS OF LIFE INITIAL
VALUE: 0 hrs
Range: 0 to 500000 hrs. in steps of 1
MESSAGE
LOSS OF LIFE PICKUP:
180000 hrs
Range: 0 to 500000 hrs. in steps of 1
MESSAGE
LOSS OF LIFE BLOCK:
Off
Range: FlexLogic™ operand
MESSAGE
LOSS OF LIFE TARGET:
Self-Reset
Range: Self-reset, Latched, Disabled
SETTING
SETTING
ACTUAL VALUE
SETTING
FLEXLOGIC OPERANDS
XFMR LIFE LOST
LOSS OF LIFE
FUNCTION:
LOSS OF LIFE
BLOCK:
LOL > PKP
RUN
LOSS OF LIFE
PICKUP:
LOSS OF LIFE OP
LOSS OF LIFE PKP
Disable=0
Enable=1
Off=0
828732A2.CDR
AND
Summary of Contents for UR T60
Page 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...