![GE UR T60 Instruction Manual Download Page 80](http://html.mh-extra.com/html/ge/ur-t60/ur-t60_instruction-manual_130388080.webp)
3-24
T60 Transformer Protection System
GE Multilin
3.2 WIRING
3 HARDWARE
3
3.2.8 RS232 FACEPLATE PORT
A 9-pin RS232C serial port is located on the T60 faceplate for programming with a personal computer. All that is required to
use this interface is a personal computer running the EnerVista UR Setup software provided with the relay. Cabling for the
RS232 port is shown in the following figure for both 9-pin and 25-pin connectors.
The baud rate for this port is fixed at
19200 bps
.
Figure 3–24: RS232 FACEPLATE PORT CONNECTION
3.2.9 CPU COMMUNICATION PORTS
a) OVERVIEW
In addition to the faceplate RS232 port, the T60 provides two additional communication ports or a managed six-port Ether-
net switch, depending on the installed CPU module. In the following table, multiple Ethernet ports are supported, but only
one can be used at a time. For example, the 10Base-F (normal) port and 10Base-T (alternate) port are supported in the 9G
module, but only one can be used at a time.
The CPU modules do not require a surge ground connection.
Table 3–3: CPU MODULE COMMUNICATIONS (MODULE APPLICABLE DEPENDS ON ORDER CODE)
CPU TYPE
COM1
COM2
9E
RS485
RS485
9G
10Base-F or 10Base-T (obsolete)
RS485
9H
Redundant 10Base-F or 10Base-T (obsolete)
RS485
9J
100Base-FX or 10/100Base-T
RS485
9K
Redundant 100Base-FX or 10/100Base-T
RS485
9L
100Base-FX (obsolete)
RS485
9M
Redundant 100Base-FX (obsolete)
RS485
9N
10/100Base-T
RS485
9S
Six-port managed Ethernet switch
RS485
NOTE
NOTE
Summary of Contents for UR T60
Page 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...