![GE UR T60 Instruction Manual Download Page 573](http://html.mh-extra.com/html/ge/ur-t60/ur-t60_instruction-manual_130388573.webp)
GE Multilin
T60 Transformer Protection System
B-35
APPENDIX B
B.4 MEMORY MAPPING
B
Neutral Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules)
5C00
Neutral Instantaneous Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5C01
Neutral Instantaneous Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5C02
Neutral Instantaneous Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5C03
Neutral Instantaneous Overcurrent 1 Delay
0 to 600
s
0.01
F001
0
5C04
Neutral Instantaneous Overcurrent 1 Reset Delay
0 to 600
s
0.01
F001
0
5C05
Neutral Instantaneous Overcurrent 1 Block
0 to 65535
---
1
F300
0
5C06
Neutral Instantaneous Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5C07
Neutral Instantaneous Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5C08
Reserved (8 items)
0 to 1
---
1
F001
0
5C10
...Repeated for Neutral Instantaneous Overcurrent 2
5C20
...Repeated for Neutral Instantaneous Overcurrent 3
5C30
...Repeated for Neutral Instantaneous Overcurrent 4
5C40
...Repeated for Neutral Instantaneous Overcurrent 5
5C50
...Repeated for Neutral Instantaneous Overcurrent 6
5C60
...Repeated for Neutral Instantaneous Overcurrent 7
5C70
...Repeated for Neutral Instantaneous Overcurrent 8
5C80
...Repeated for Neutral Instantaneous Overcurrent 9
5C90
...Repeated for Neutral Instantaneous Overcurrent 10
5CA0
...Repeated for Neutral Instantaneous Overcurrent 11
5CB0
...Repeated for Neutral Instantaneous Overcurrent 12
Ground Time Overcurrent (Read/Write Grouped Setting) (6 modules)
5D00
Ground Time Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5D01
Ground Time Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5D02
Ground Time Overcurrent 1 Input
0 to 1
---
1
F122
0 (Phasor)
5D03
Ground Time Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5D04
Ground Time Overcurrent 1 Curve
0 to 16
---
1
F103
0 (IEEE Mod Inv)
5D05
Ground Time Overcurrent 1 Multiplier
0 to 600
---
0.01
F001
100
5D06
Ground Time Overcurrent 1 Reset
0 to 1
---
1
F104
0 (Instantaneous)
5D07
Ground Time Overcurrent 1 Block
0 to 65535
---
1
F300
0
5D08
Ground Time Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5D09
Ground Time Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5D0A
Reserved (6 items)
0 to 1
---
1
F001
0
5D10
...Repeated for Ground Time Overcurrent 2
5D20
...Repeated for Ground Time Overcurrent 3
5D30
...Repeated for Ground Time Overcurrent 4
5D40
...Repeated for Ground Time Overcurrent 5
5D50
...Repeated for Ground Time Overcurrent 6
Ground Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules)
5E00
Ground Instantaneous Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5E01
Ground Instantaneous Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5E02
Ground Instantaneous Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5E03
Ground Instantaneous Overcurrent 1 Delay
0 to 600
s
0.01
F001
0
5E04
Ground Instantaneous Overcurrent 1 Reset Delay
0 to 600
s
0.01
F001
0
5E05
Ground Instantaneous Overcurrent 1 Block
0 to 65535
---
1
F300
0
5E06
Ground Instantaneous Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5E07
Ground Instantaneous Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5E08
Reserved (8 items)
0 to 1
---
1
F001
0
5E10
...Repeated for Ground Instantaneous Overcurrent 2
5E20
...Repeated for Ground Instantaneous Overcurrent 3
5E30
...Repeated for Ground Instantaneous Overcurrent 4
5E40
...Repeated for Ground Instantaneous Overcurrent 5
5E50
...Repeated for Ground Instantaneous Overcurrent 6
5E60
...Repeated for Ground Instantaneous Overcurrent 7
Table B–10: MODBUS MEMORY MAP (Sheet 27 of 65)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for UR T60
Page 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...