GE Multilin
T60 Transformer Protection System
2-11
2 PRODUCT DESCRIPTION
2.2 SPECIFICATIONS
2
GROUND DISTANCE
Characteristic:
Mho (memory polarized or offset) or
Quad (memory polarized or non-direc-
tional), selectable individually per zone
Reactance polarization: negative-sequence or zero-sequence
current
Non-homogeneity angle: –40 to 40° in steps of 1
Number of zones:
3
Directionality:
forward, reverse, or non-directional per
zone
Reach (secondary
Ω
):
0.02 to 500.00
Ω
in steps of 0.01
Reach accuracy:
±5% including the effect of CVT tran-
sients up to an SIR of 30
Distance characteristic angle: 30 to 90° in steps of 1
Distance comparator limit angle: 30 to 90° in steps of 1
Directional supervision:
Characteristic angle:
30 to 90° in steps of 1
Limit angle:
30 to 90° in steps of 1
Zero-sequence compensation
Z0/Z1 magnitude:
0.00 to 10.00 in steps of 0.01
Z0/Z1 angle:
–90 to 90° in steps of 1
Zero-sequence mutual compensation
Z0M/Z1 magnitude:
0.00 to 7.00 in steps of 0.01
Z0M/Z1 angle:
–90 to 90° in steps of 1
Right blinder (Quad only):
Reach:
0.02 to 500
Ω
in steps of 0.01
Characteristic angle:
60 to 90° in steps of 1
Left blinder (Quad only):
Reach:
0.02 to 500
Ω
in steps of 0.01
Characteristic angle:
60 to 90° in steps of 1
Time delay:
0.000 to 65.535 s in steps of 0.001
Timing accuracy:
±3% or 4 ms, whichever is greater
Current supervision:
Level:
neutral current (3I_0)
Pickup:
0.050 to 30.000 pu in steps of 0.001
Dropout:
97 to 98%
Memory duration:
5 to 25 cycles in steps of 1
Voltage supervision pickup (series compensation applications):
0 to 5.000 pu in steps of 0.001
Operation time:
1 to 1.5 cycles (typical)
Reset time:
1 power cycle (typical)
RESTRICTED GROUND FAULT
Pickup:
0.005 to 30.000 pu in steps of 0.001
Dropout:
97 to 98% of pickup
Slope:
0 to 100% in steps of 1%
Level accuracy:
0.1 to 2.0 x CT rating: ±0.5% of reading or ±1% of rated (which-
ever is greater)
>2.0 x CT rating
±1.5% of reading
Pickup delay:
0 to 600.00 s in steps of 0.01
Dropout delay:
0 to 600.00 s in steps of 0.01
Operate time:
<1 power system cycle
PHASE/NEUTRAL/GROUND TOC
Current:
Phasor or RMS
Pickup level:
0.000 to 30.000 pu in steps of 0.001
Dropout level:
97% to 98% of pickup
Level accuracy:
0.1 to 2.0
×
CT:
±0.5% of reading or ±0.4% of rated
(whichever is greater)
> 2.0
×
CT:
±1.5% of reading > 2.0
×
CT rating
Curve shapes:
IEEE Moderately/Very/Extremely
Inverse; IEC (and BS) A/B/C and Short
Inverse; GE IAC Inverse, Short/Very/
Extremely Inverse; I
2
t; FlexCurves™
(programmable); Definite Time (0.01 s
base curve)
Curve multiplier:
Time Dial = 0.00 to 600.00 in steps of
0.01
Reset type:
Instantaneous/Timed (per IEEE)
Timing accuracy:
Operate at > 1.03
×
actual pickup
±3.5% of operate time or ±½ cycle
(whichever is greater)
Voltage restraint:
Modifies pickup current for voltage in the
range of 0.1<V<0.9 VT Nominal in a
fixed linear relationship
PHASE/NEUTRAL/GROUND IOC
Pickup level:
0.000 to 30.000 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Level accuracy:
0.1 to 2.0
×
CT rating: ±0.5% of reading or ±0.4% of rated
(whichever is greater)
> 2.0
×
CT rating
±1.5% of reading
Overreach:
<2%
Pickup delay:
0.00 to 600.00 s in steps of 0.01
Reset delay:
0.00 to 600.00 s in steps of 0.01
Operate time:
<16 ms at 3
×
pickup at 60 Hz
(Phase/Ground IOC)
<20 ms at 3
×
pickup at 60 Hz
(Neutral IOC)
Timing accuracy:
Operate at 1.5
×
pickup
±3% or ±4 ms (whichever is greater)
PHASE DIRECTIONAL OVERCURRENT
Relay connection:
90
°
(quadrature)
Quadrature voltage:
ABC phase seq.: phase A (V
BC
), phase
B (V
CA
), phase C (V
AB
); ACB phase
seq.: phase A (V
CB
), phase B (V
AC
),
phase C (V
BA
)
Polarizing voltage threshold: 0.000 to 3.000 pu in steps of 0.001
Current sensitivity threshold: 0.05 pu
Characteristic angle:
0 to 359
°
in steps of 1
Angle accuracy:
±2°
Operation time (FlexLogic™ operands):
Tripping (reverse load, forward fault):
<
12 ms, typically
Blocking (forward load, reverse fault):
<
8 ms, typically
Summary of Contents for UR T60
Page 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...