Proline Promass F 200 HART
Diagnostics and troubleshooting
Hauser
97
No write access to parameters
Current user role has limited access
authorization
2. Enter correct customer-specific
access code (
No connection via HART protocol
Missing or incorrectly installed
communication resistor.
Install the communication resistor (250
W
) correctly. Observe the maximum
No connection via HART protocol
Commubox
• Connected incorrectly
• Configured incorrectly
• Drivers not installed correctly
• USB interface on computer
configured incorrectly
Observe the documentation for the
Commubox.
FXA195 HART: Document
"Technical Information"
TI00404F
No connection via service interface
Incorrect configuration of USB interface
on PC or driver not installed correctly.
Observe the documentation for the
Commubox.
FXA291: Document "Technical
Information" TI00405C