Proline Promass F 200 HART
Commissioning
Hauser
67
Reference density unit
Select the unit for reference
density.
Result
The selected unit applies for:
– Outputs
– Low value partial filled
pipe detection
– High value partial filled
pipe detection
– Simulation process
variable
– Fixed reference density
– Density adjustment (in the
Expert
menu)
Unit choose list
Country-dependent:
• kg/Nl
• lb/scf
Temperature unit
Select the unit for
temperature.
Result
The selected unit applies for:
– Outputs
– Reference temperature
– Simulation process
variable
Unit choose list
Country-dependent:
•
°
C (Celsius)
•
°
F (Fahrenheit)
Unit totalizer
Select the unit for the process
variable of the totalizer.
Unit choose list
Depends on country and
nominal diameter
Switch-on value
Enter the measured value for
the switch-on value.
Depends on the process
variable selected
-
Switch-off value
Enter the measured value for
the switch-off value.
Depends on the process
variable selected
-
Switch-on delay
Specify the delay time for
switching on the switch
output.
0.0 to 100.0 s
0.0 s
Switch-off delay
Specify the delay time for
switching off the switch
output.
0.0 to 100.0 s
0.0 s
Failure mode
Specify the output behavior
in the event of a device
alarm.
• Current status
• Open
• Closed
Open
Invert output signal
Invert the output signal.
• No
• Yes
No
10.4.4 Configuring the local display
The
Display
wizard guides you systematically through all parameters that can configured for
configuring the local display.
Navigation path
"Setup" menu
®
Display