Proline Promass F 200 HART
Technical data
Hauser
117
17
Technical data
17.1
Application
The measuring device is suitable for flow measurement of liquids and gases only.
Depending on the version ordered, the measuring device can also measure potentially explosive,
flammable, poisonous and oxidizing media.
To ensure that the device remains in proper operating condition for its service life, use the measuring
device only for media against which the process-wetted materials are adequately resistant.
17.2
Function and system design
Measuring principle
Mass flow measurement based on the Coriolis measuring principle
Measuring system
The device consists of a transmitter and a sensor.
One device version is available: compact version, transmitter and sensor form a mechanical unit.
For information on the structure of the device (
17.3
Input
Measured variable
Direct measured variables
• Mass flow
• Density
• Temperature
Calculated measured variables
• Volume flow
• Corrected volume flow
• Reference density
Measuring range
Measuring ranges for liquids
DN
Measuring range full scale values
g
min(F)
to
g
max(F)
[mm]
[in]
[kg/h]
[lb/min]
8
3/8
0 to 2
000
0 to 73.5
15
½
0 to 6
500
0 to 238
25
1
0 to 18
000
0 to 660
40
1 ½
0 to 45
000
0 to 1
650
50
2
0 to 70
000
0 to 2
570
Measuring ranges for gases
The full scale values depend on the density of the gas and can be calculated with the formula below:
g
max(G)
=
g
max(F)
×
r
G
:
x