Proline Promass F 200 HART
Technical data
Hauser
121
17.5
Power supply
Terminal assignment
Supply voltage
An external power supply is required for each output. The following supply voltage values apply for
the 4-20 mA and 4-20 mA HART current output:
Order code for
"Output"
Minimum terminal voltage
1)
2)
Maximum terminal voltage
• Option
A
: 4-20 mA HART
• Option
B
: 4-20 mA HART, pulse/
frequency/switching output
For 4 mA:
³
DC18 V
For 20 mA:
³
DC14 V
DC35 V
Option
C
: 4-20 mA HART, 4-20 mA
For 4 mA:
³
DC 18 V
For 20 mA:
³
DC 14 V
DC30 V
1)
External supply voltage of the power supply unit with load (
2)
For device versions with local display SD03: The terminal voltage must be increased by DC 2 V if backlighting is used.
Power consumption
Transmitter
Order code for
"Output"
Maximum power consumption
Option
A
: 4-20 mA HART
770 mW
Option
B
: 4-20 mA HART, pulse/frequency/switching
output
• Operation with output 1:770 mW
• Operation with output 1 and 2:2
770 mW
Option
C
: 4-20 mA HART, 4-20 mA
• Operation with output 1:660 mW
• Operation with output 1 and 2:1
320 mW
Current consumption
For every 4-20 mA or 4-20 mA HART current output: 3.6 to 22.5 mA
If the option
Defined value
is selected in the
Failure mode
3.59 to 22.5 mA
Power supply failure
• Totalizers stop at the last value measured.
• Configuration is retained in the device memory (HistoROM).
• Error messages (incl. total operated hours) are stored.
Electrical connection
Potential equalization
No special measures for potential equalization are required.
Terminals
• For device version without integrated overvoltage protection: plug-in spring terminals for wire
cross-sections 0.5 to 2.5 mm
2
(20 to 14 AWG)
• For device version with integrated overvoltage protection: screw terminals for wire cross-sections
0.2 to 2.5 mm
2
(24 to 14 AWG)
Cable entries
• Cable gland: M20 × 1.5 with cable
Æ
6 to 12 mm (0.24 to 0.47 in)
• Thread for cable entry:
– NPT ½"
– G ½"