Proline Promass F 200 HART
Technical data
Hauser
119
Maximum input values
• DC35 V
• 50 mA
For information on the Ex connection values
Voltage drop
• For
£
2 mA: 2 V
• For 10 mA: 8 V
Residual current
£
0.05 mA
Pulse output
Pulse width
Adjustable:5 to 2
000 ms
Maximum pulse rate
100 Impulse/s
Pulse value
Adjustable
Assignable measured
variables
• Mass flow
• Volume flow
• Corrected volume flow
Frequency output
Output frequency
Adjustable:0 to 1
000 Hz
Damping
Adjustable:0 to 999 s
Pulse/pause ratio
1:1
Assignable measured
variables
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
Switching output
Switching behavior
Binary, conductive or non-conductive
Switching delay
Adjustable:0 to 100 s
Number of switching cycles
Unlimited
Assignable functions
• Off
• On
• Diagnostic behavior
• Limit value
– Mass flow
– Volume flow
– Corrected volume flow
– Density
– Reference density
– Temperature
– Totalizer 1-3
• Flow direction monitoring
• Status
– Partial filled pipe detection
– Low flow cut off
Signal on alarm
Depending on the interface, failure information is displayed as follows:
Current output
4-20 mA
Failure mode
Selectable (as per NAMUR recommendation NE 43):
• Minimum alarm:3.6 mA
• Maximum alarm:22 mA
• Adjustable value:3.59 to 22.5 mA