Proline Promass F 200 HART
Commissioning
Hauser
71
Parameter overview with brief description
Parameters
Description
Selection/
User entry
Factory setting
Level of flow fluctuation
Specify the extent measured
values fluctuate due to
changes in the process.
Result
Depending on the selection
made here, a recommended
value range is displayed
when entering the reaction
time (damping) of the local
display or the outputs.
• Slight
• Moderate
• Strong
Moderate
Display damping
Set the reaction time of the
local display to fluctuations in
the measured value caused
by process conditions.
0 to 999 s
0 s
Damping output 1-2
Set the reaction time of the
current output signal to
fluctuations in the measured
value caused by process
conditions.
0 to 999 s
1 s
Measuring mode output 1-2 Select the measuring mode
for current output.
• Forward flow
• Forward/reverse flow
• Reverse flow
compensation
Forward flow
Totalizer operation mode 1-3 Select totalizer calculation
mode
• Net flow total
• Forward flow total
• Reverse flow total
Net flow total
Assign process variable
Select process variable for
low flow cut off
• Off
• Mass flow
• Volume flow
• Corrected volume flow
Mass flow
On value low flow cutoff
Enter the on value for low
flow cutoff.
Max. 15-digit, positive
floating-point number
For liquids: depends on
country and nominal
diameter
Off value low flow cut off
Enter off value for low flow
cut off
0 to 100
%
50
%
Pressure shock suppression
Enter time frame for signal
suppression (= active
pressure shock suppression)
0 to 100 s
0 s