Proline Promass F 200 HART
Electrical connection
Hauser
27
Calculation of the maximum load
Depending on the supply voltage of the power supply unit (U
S
), the maximum load (R
B
) including
line resistance must be observed to ensure adequate terminal voltage at the device. In doing so,
observe the minimum terminal voltage (
• For U
S
= 18 to 18.9 V: R
B
£
(U
S
- 18 V)
:
0.0036 A
• For U
S
= 18.9 to 24.5 V: R
B
£
(U
S
- 13.5 V)
:
0.022 A
• For U
S
= 24.5 to 30 V: R
B
£
500
W
0
100
200
300
400
500
14
16
18
20
22
24
26
28
30
32
U [V]
s
R [
]
b
W
1.1
1.2
1
34
36
A0013563
1
Operating range
1.1 For order code for "Output", option A "4-20mA HART"/option B "4-20mA HART, pulse/frequency/switch output"
with Ex i and option C "4-20mA HART, 4-20mA"
1.2 For order code for "Output", option A "4-20mA HART"/option B "4-20mA HART, pulse/frequency/switch output"
with non-Ex and Ex d
Sample calculation
Supply voltage of the power supply unit: U
S
=19 V
Maximum load: R
B
£
(19 V - 13.5 V)
:
0.022 A = 250
W
7.1.5
Preparing the measuring device
1. Remove dummy plug if present.
2.
NOTICE!
Insufficient sealing of the housing! Operational reliability of the measuring device
could be compromised. Use suitable cable glands corresponding to the degree of protection.
If measuring device is delivered without cable glands:
Provide suitable cable gland for corresponding connecting cable (
3. If measuring device is delivered with cable glands:
7.2
Connecting the measuring device
NOTICE
Limitation of electrical safety due to incorrect connection!
►
Have electrical connection work carried out by correspondingly trained specialists only.
►
Observe applicable federal/national installation codes and regulations.
►
Comply with local workplace safety regulations.
►
For use in potentially explosive atmospheres, observe the information in the device-specific Ex
documentation.