C.Chg
SMARTCARD trip: Data location already contains data
179
Erase data in data location
Write data to an alternative data location
C.cPr
SMARTCARD trip: The values stored in the drive and the values in the data block on the SMARTCARD are different
188
Press the red
reset button
C.dAt
SMARTCARD trip: Data location specified does not contain any data
183
Ensure data block number is correct
C.Err
SMARTCARD trip: SMARTCARD data is corrupted
182
Ensure the card is located correctly
Erase data and retry
Replace SMARTCARD
C.Full
SMARTCARD trip: SMARTCARD full
184
Delete a data block or use different SMARTCARD
cL2
Analog input 2 current loss (current mode)
28
Check analog input 2 (terminal 7) current signal is present (4-20mA, 20-4mA)
cL3
Analog input 3 current loss (current mode)
29
Check analog input 3 (terminal 8) current signal is present (4-20mA, 20-4mA)
CL.bit
Trip initiated from the control word (Pr 6.42)
35
Disable the control word by setting Pr
6.43
to 0 or check setting of Pr
6.42
ConF.P
The number of power modules installed no longer matches the value stored in Pr 11.35
111
Ensure that all power modules are correctly connected
Ensure that all power modules have powered up correctly
Ensure that the value in Pr
11.35
matches the number of power modules connected
C.OPtn
SMARTCARD trip: Solutions Modules installed are different between source drive and destination drive
180
Ensure correct Solutions Modules are installed
Ensure Solutions Modules are in the same Solutions Module slot
Press the red
reset button
C.Prod
SMARTCARD trip: The data blocks on the SMARTCARD are not compatible with this product
175
Erase all data on the SMARTCARD by setting Pr
xx.00
to 9999 and pressing the red
reset button
Replace SMARTCARD
C.rdo
SMARTCARD trip: SMARTCARD has the Read Only bit set
181
Enter 9777 in Pr
xx.00
to allow SMARTCARD Read / Write access
Ensure the drive is not writing to data locations 500 to 999 on the card
Trip
Diagnosis