Menu 10
Parameter
structure
Keypad and
display
Parameter
x.00
Parameter
description format
Advanced parameter
descriptions
Macros
Serial comms
protocol
Electronic
nameplate
Performance RFC mode
178
Unidrive SP Advanced User Guide
www.controltechniques.com Issue Number: 10
5.12 Menu 10: Status and trips
Indicates the drive is not in the trip state. If Pr
10.36
is one and auto-reset is being used, this bit is not cleared until all auto-resets have been
attempted and the next trip occurs. The control board LED reflects the state of this parameter: LED on continuously = 1, LED flashing = 0.
Indicates that the drive inverter is active.
Open-loop
Indicates that the absolute value of the ramp output (|Pr
2.01
|) is at or below the zero speed threshold defined by Pr
.
Closed-loop and Servo
Indicates that the absolute value of speed feedback (|Pr
3.02
|) is at or below the zero speed threshold defined by Pr
.
In bipolar mode (Pr
1.10
= 1) this parameter is the same as zero speed (Pr
10.03
). In unipolar mode this parameter is set if the absolute value of the
ramp output (Pr
2.01
) or speed feedback (Pr
3.02
) is at or below (minimum speed + 0.5Hz), or (minimum speed + 5rpm). Minimum speed is defined
by Pr
1.07
. The parameter is only set if the drive is running.
10.01
Drive ok
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
Update rate
Background write
10.02
Drive active
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
Update rate
4ms write
10.03
Zero speed
Drive modes
Open-loop, Closed-loop vector, Servo
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
Update rate
Background write
10.04
Running at or below min speed
Drive modes
Open-loop, Closed-loop vector, Servo
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
Update rate
Background write
10.05
Below set speed
Drive modes
Open-loop, Closed-loop vector, Servo
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
Update rate
Background write
10.06
At speed
Drive modes
Open-loop, Closed-loop vector, Servo
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
Update rate
Background write
Summary of Contents for unidrive sp