Parameter
structure
Keypad and
display
Parameter
x.00
Parameter
description format
Advanced parameter
descriptions
Macros
Serial comms
protocol
Electronic
nameplate
Performance RFC mode
Menu 3
Regen
Unidrive SP Advanced User Guide
85
Issue Number: 10 www.controltechniques.com
The sinusoidal rectifier unit will attempt to hold the DC bus at the level specified by this parameter. The bus voltage must always be higher than the
peak of the line to line supply voltage if the unit is to operate correctly. The default values can be used with most supplies giving a reasonable level of
control headroom. However, with higher voltage supplies the set-point must be raised.
When the drive is operated as a regen unit it uses a DC bus voltage controller with inner current controllers as shown below.
The gains of the voltage and current controllers affect the stability of the regen unit control system and incorrect gain settings can result in over-
voltage or over-current trips. In many applications the default gains given for the current controllers (Pr
4.13
and Pr
4.14
) will be suitable, however, it
may be necessary for the user to change these if the inductance or resistance of the supply plus the regen inductors varies significantly from the
expected values.
Setting the current controller gains
The most critical parameter for stability is the current controller proportional gain (Pr
4.13
). The required value for this is dependent on the regen unit
input inductance. If the inductance of the supply is a significant proportion of the recommended regen inductor (i.e. 60/I
DR
mH per phase, where I
DR
is equivalent to Kc), then the proportional gain may need to be increased. The supply inductance is likely to be negligible compared to the regen
inductor value with small drives, but is likely to be significant with larger drives. The proportional gain should be adjusted as described for Pr
4.13
(closed-loop modes) using the total inductance per phase. The current controller integral gain is not so critical, and in a majority of cases the default
value is suitable. However, if it is necessary to adjust this parameter it should be set up as described for Pr
4.14
(closed-loop modes) using the supply
resistance for one phase.
Setting the voltage controller gain
Even when the gains are set correctly there will be a transient change of DC bus voltage when there is a change in the load on any drive connected
to the regen unit. This can be reduced substantially by using an analog input for power feed forward compensation (see Pr
3.10
). The following
discussion relates to a system without power feed-forward compensation.
If the power flow from the supply is increased (i.e. more power is taken from the supply or less power is fed back into the supply) the DC bus voltage
will fall, but the minimum level will be limited to just below the peak rectified level of the supply provided the maximum rating of the unit is not
exceeded. If the power flow from the supply is reduced (i.e. less power is taken from the supply or more power is fed back into the supply) the DC bus
voltage will rise. During a rapid transient the bus will rise and then fall as shown below.
3.05
Voltage set-point
Drive modes
Regen
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
1
Range
Regen
0 to DC_VOLTAGE_SET_MAX V
Default
Regen
200V rating drive: 350
400V rating drive: 700
575V rating drive: 835
690V rating drive: 1100
Update rate
Background read
3.06
Voltage controller Kp gain
Drive modes
Regen
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
Range
Regen
0 to 65,535
Default
Regen
4,000
Update rate
Background read
Voltage
controller
Current
controllers
-
-
DC bus
voltage
feedback
Current
feedback
Pr
DC
bus voltage
set point
3.05
Summary of Contents for unidrive sp
Page 419: ......
Page 420: ...0471 0002 10 ...