Unidrive SP Advanced User Guide
341
Issue Number: 10 www.controltechniques.com
The error status is provided so that only one Solutions Module error trip is required for each Solutions Module slot. If an error occurs the reason for
the error is written to this parameter and the drive may produce a SLx.Er trip, where x is the slot number. A value of zero indicates that the module has
not detected an error, a non-zero value indicates that an error has been detected. (See Table 5-36 on page 336 for the meaning of the values in this
parameter). When the drive is reset this parameter is cleared for all Solutions Modules.
All modules include a temperature monitoring circuit. If the PCB temperature exceeds 90°C the drive fan is forced to operate at full speed (for a
minimum of 10s). If the temperature falls below 90°C the fan can operate normally again. If the PCB temperature exceeds 100°C the drive is tripped
and the error status is set to 74.
Most Solutions Modules include a processor with software. The software version is displayed in these parameters in the form Pr
x.02
= xx.yy and
Pr
x.50
= zz. Where xx specifies a change that affects hardware compatibility, yy specifies a change that affects product documentation, and zz
specifies a change that does not affect the product documentation. When a module is installed that does not contain software both these parameters
appear as zero.
x.50
Solutions Module error status
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU
PS
1
1
1
1
Range
Open-loop, Closed-loop, Servo, Regen
0 to 255
Update rate
Background write
x.51
Solutions Module software sub-version
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU
PS
1
1
1
1
Range
Open-loop, Closed-loop, Servo, Regen
0 to 99
Update rate
Write on power-up
Summary of Contents for unidrive sp