Parameter
structure
Keypad and
display
Parameter
x.00
Parameter
description format
Advanced parameter
descriptions
Macros
Serial comms
protocol
Electronic
nameplate
Performance RFC mode
Menus 15 to 17
SM-I/O 32
Unidrive SP Advanced User Guide
325
Issue Number: 10 www.controltechniques.com
The parameter specified in these parameters by the user is the source parameter when corresponding digital I/O line is set as an output or destination
parameter when corresponding digital I/O line is set as an input. A total of 8 source or destination parameters can be defined. Pr
x.21
to Pr
x.28
corresponds to bits 0 to 7 (DIO1 to DIO8) respectively.
When the output select parameter for an I/O line is set to On, the I/O is set up as an output as follows:
The drive parameter defined by this parameter is the direction register for the fast update method. Setting the relevant bit to 1 within the direction
register parameter will select the corresponding I/O line to function as an output. If this parameter is set to
0.00
or a non existent parameter then all
I/O lines are defined as inputs for the fast update method. The direction register parameter range may not be large enough to allow all I/O lines to be
controlled. Any bits that cannot be controlled are assumed to be zero and the corresponding I/O lines are defined as inputs for the fast update
method.
The drive parameter defined by this parameter is the read register for the fast update method. When an I/O line is set up as an input for the fast
update method the corresponding bit in the read register shows the state of the input. Bits that correspond to I/O lines that are set as outputs in the
direction register or in the direction registers for the standard update method show the state of the output I/O line. If this parameter is set to
0.00
or a
non existent parameter then no read register is defined. The read register parameter range may not be large enough to allow the state of all I/O lines
to be shown; in this case the value containing the I/O status for all 32 I/O lines will be limited to the read register parameter range before being written
to the read register parameter.
x.21
Digital I/O 1 source/destination
x.22
Digital I/O 2 source/destination
x.23
Digital I/O 3 source/destination
x.24
Digital I/O 4 source/destination
x.25
Digital I/O 5 source/destination
x.26
Digital I/O 6 source/destination
x.27
Digital I/O 7 source/destination
x.28
Digital I/O 8 source/destination
RW
Uni
DE
PT
US
Ú
Pr
0.00
to Pr
21.51
Ö
Pr
0.00
Update rate: Read on drive reset
x.29
Digital I/O 4 output select
RW
Bit
PT
US
Ú
OFF (0) or On (1)
Ö
OFF (0)
Update rate: Background read
x.31
Digital I/O 1 output select
x.32
Digital I/O 2 output select
x.33
Digital I/O 3 output select
RW
Bit
US
Ú
OFF (0) or On (1)
Ö
OFF (0)
Update rate: Background read
Digital I/O
Output select
DIO1
Pr
x.31
DIO2
Pr
x.32
DIO3
Pr
x.33
DIO4
Pr
x.29
x.43
Fast update method direction register
RW
Uni
DE
PT
US
Ú
Pr
0.00
to Pr
21.51
Ö
Pr
0.00
Update rate: Read on drive reset
x.47
Fast update method read register
RW
Uni
DE
PT
US
Ú
Pr
0.00
to Pr
21.51
Ö
Pr
0.00
Update rate: Read on drive reset