Menu 11
Parameter
structure
Keypad and
display
Parameter
x.00
Parameter
description format
Advanced parameter
descriptions
Macros
Serial comms
protocol
Electronic
nameplate
Performance RFC mode
206
Unidrive SP Advanced User Guide
www.controltechniques.com Issue Number: 10
ANSIx3.28 protocol
Full details of the CT implementation of ANSIx3.28 are given in Chapter 7
Serial communications protocol
Modbus RTU protocol
Full details of the CT implementation of Modbus RTU are given in Chapter 7
Serial communications protocol
The protocol provides the following facilities:
•
Drive parameter access with basic Modbus RTU
•
The protocol supports access to 32 bit floating point parameters
The following product specific limitations apply:
•
Maximum slave response time when accessing the drive is 100ms
•
Maximum number of 16 bit registers that can be written to, or read from, the drive itself is limited to 16
•
Maximum number of 16 bit registers that can be written to, or read from, a Solutions Module or via a Solutions Module - see Solutions Module
User Guide
•
The communications buffer can hold a maximum of 128bytes
Modbus RTU protocol, but with SM-Keypad Plus only
This setting is used for disabling comms access when the SM-Keypad Plus is used as a hardware key. See the SM-Keypad Plus User Guide for more
information.
Used in all comms modes to define the baud rate.
*Modbus RTU only
This parameter can be changed via the drive keypad, via a Solutions Module or via the comms interface itself. If it is changed via the comms
interface, the response to the command uses the original baud rate. The master should wait at least 20ms before sending a new message using the
new baud rate.
Parameter value
String
Comms mode
0
AnSI ANSIx3.28
protocol
1
rtU
Modbus RTU protocol
2
Lcd
Modbus RTU protocol, but only with an LCD keypad
11.25
Baud rate
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV PT US RW BU PS
1
1
1
1
Range
Open-loop, Closed-loop vector, Servo,
Regen
0 to 9
Default
Open-loop, Closed-loop vector, Servo,
Regen
6
Update rate
Background read
Parameter value
String/baud rate
0
300
1
600
2
1200
3
2400
4
4800
5
9600
6
19200
7
38400
8*
57600
9*
115200