Menu 1
Parameter
structure
Keypad and
display
Parameter
x.00
Parameter
description format
Advanced parameter
descriptions
Macros
Serial comms
protocol
Electronic
nameplate
Performance RFC mode
32
Unidrive SP Advanced User Guide
www.controltechniques.com Issue Number: 10
Reference used for jogging. See section 5.8
on page 134 for details on when the jog mode can be activated. The jog
reference can be used for relative jogging in digital lock mode (see section 5.15
1.01
Frequency/speed reference selected
Drive modes
Open-loop, Closed-loop vector, Servo
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
1
Range
Open-loop, Closed-loop vector, Servo
±SPEED_FREQ_MAX Hz/rpm
Update rate
4ms write
1.02
Pre-skip filter reference
Drive modes
Open-loop, Closed-loop vector, Servo
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
1
Range
Open-loop, Closed-loop vector, Servo
±SPEED_FREQ_MAX Hz/rpm
Update rate
4ms write
1.03
Pre-ramp reference
Drive modes
Open-loop, Closed-loop vector, Servo
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
1
Range
Open-loop, Closed-loop vector, Servo
±SPEED_FREQ_MAX Hz/rpm
Update rate
4ms write
1.04
Reference offset
Drive modes
Open-loop, Closed-loop vector, Servo
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
Range
Open-loop
Closed-loop vector, Servo
±3,000.0 Hz
±40,000.0 rpm
Default
Open-loop, Closed-loop vector. Servo
0
Update rate
Background read when precision reference is active
4ms write otherwise
1.05
Jog reference
Drive modes
Open-loop, Closed-loop vector, Servo
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
Range
Open-loop
Closed-loop vector, Servo
0 to 400.0 Hz
0 to 4,000.0 rpm
Default
Open-loop, Closed-loop vector, Servo
0.0
Update rate
4ms read
Summary of Contents for unidrive sp
Page 419: ......
Page 420: ...0471 0002 10 ...