Menu 21
Parameter
structure
Keypad and
display
Parameter
x.00
Parameter
description format
Advanced parameter
descriptions
Macros
Serial comms
protocol
Electronic
nameplate
Performance RFC mode
360
Unidrive SP Advanced User Guide
www.controltechniques.com Issue Number: 10
Pr
21.12
shows the stator resistance of the motor. The units vary with the drive size to ensure that the full range of likely resistances can be
represented with suitable resolution. The table below shows the units. Therefore 1.000 in the parameter represents the resistance shown in the units
column.
s
21.09
Rated voltage
Drive modes
Open-loop, Closed-loop vector, Servo
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU
PS
1
1
1
1
1
Range
Open-loop, Closed-loop vector, Servo
0 to AC_VOLTAGE_SET_MAX V
Default
Open-loop, Closed-loop vector, Servo
200V rating drive: 230V
400V rating drive: EUR: 400V, USA: 460V
575V rating drive: 575V
690V rating drive: 690V
Normal
parameter
Open-loop, Closed-loop vector, Servo
Pr
5.09
Update rate
Level 4 read
21.10
Rated power factor
Drive modes
Open-loop, Closed-loop vector
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU
PS
3
1
1
1
1
Range
Open-loop, Closed-loop vector
0.000 to 1.000
Default
Open-loop, Closed-loop vector
0.850
Normal
parameter
Open-loop, Closed-loop vector
Pr
5.10
Update rate
Background read
21.11
Number of motor poles
Drive modes
Open-loop, Closed-loop vector, Servo
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU
PS
1
1
1
1
Range
Open-loop, Closed-loop vector, Servo
0 to 60 (Auto to 120 POLE)
Default
Open-loop, Closed-loop vector
Servo
0 (Auto)
3 (6 POLE)
Normal
parameter
Open-loop, Closed-loop vector, Servo
Pr
5.11
Update rate
Background read
21.12
Stator resistance
Drive modes
Open-loop, Closed-loop vector, Servo
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU
PS
3
1
1
1
1
Range
Open-loop, Closed-loop vector, Servo
0.000 to 65.000
Default
Open-loop, Closed-loop vector, Servo
0.000
Normal
parameter
Open-loop, Closed-loop vector, Servo
Pr
5.17
Update rate
Background read
Drive size
Units
Ω
SP0xxx
10.0
SP1xxx to SP5xxx
1.0
SP6xxx to SP9xxx and SPMxxxxx
0.01
Summary of Contents for unidrive sp