Unidrive SP Advanced User Guide
113
Issue Number: 10 www.controltechniques.com
Open-loop
Although the range for scaling purposes is ±SPEED_FREQ_MAX, the actual parameter value can be increased beyond this range by slip
compensation. This parameter gives the output frequency of the drive, i.e. the sum of the post ramp reference and the slip compensation.
Closed-loop vector and Servo
In these modes the output frequency is not controlled directly, and so the output frequency displayed in this parameter is calculated by measuring the
frequency of the controller reference frame.
Regen
In Regen mode the supply frequency is shown. Negative values indicate negative phase rotation of the supply.
This is the modulus of the r.m.s. line to line voltage at the inverter output at the drive output frequency.
Open-loop, Closed-loop vector and Servo modes
The output power is the dot product of the output voltage and current vectors. Positive power indicates power flowing from the drive to the motor
(motoring) and negative power indicates power flowing from the motor to the drive (regen).
Regen mode
The output power is the dot product of the output voltage and current vectors. Positive power indicates power flowing from the supply to the drive, and
negative power indicates power flowing from the drive to the supply.
The motor rpm is calculated from the post ramp reference (Pr
2.01
) for normal operation, or the slave frequency demand (Pr
3.01
) if frequency slaving
is being used. The speed of rotation is calculated as follows:
rpm = 60 x frequency / no. of pole pairs
This calculation relies on the number of motor poles being set up correctly in Pr
5.11
, or if auto mode is selected (Pr
5.11
= 0) then it relies on a
reasonably accurate value of motor rated speed being set in Pr
5.08
to allow correct calculation of the motor poles. If frequency slaving is being used
there will be an error due to the slip frequency. However, in normal operation the result will be reasonably accurate provided that the slip
compensation has been set up correctly in the rated full load rpm parameter (Pr
5.08
).
5.01
Output frequency
Drive modes
Open-loop, Closed-loop vector
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV
PT
US RW BU PS
1
1
1
1
1
1
RFC: VM = 0
Range
Open-loop
RFC
±SPEED_FREQ_MAX Hz
±1250.0 Hz
Update rate
250
μ
s write
5.02
Output voltage
Drive modes
Open-loop, Closed-loop vector
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV
PT
US RW BU PS
1
1
1
1
1
Range
Open-loop, Closed-loop vector, Servo,
Regen
0 to AC_VOLTAGE_MAX V
Update rate
Background write
5.03
Output power
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV PT US RW BU PS
1
1
2
1
1
1
Range
Open-loop, Closed-loop vector, Servo,
Regen
±POWER_MAX kW
Update rate
Background write
5.04
Motor rpm
Drive modes
Open-loop
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV
PT
US RW BU PS
1
1
1
1
Range
Open-loop
±180,000 rpm
Update rate
Background write