Parameter
structure
Keypad and
display
Parameter
x.00
Parameter
description format
Advanced parameter
descriptions
Macros
Serial comms
protocol
Electronic
nameplate
Performance RFC mode
Menu 10
Unidrive SP Advanced User Guide
193
Issue Number: 10 www.controltechniques.com
SLX.Er
Solutions Module slot X trip: Solutions Module in slot X has detected a fault
202,207,212
SLM module category
Check value in Pr
15
/
16
/
17.50
. The following table lists the possible error codes for the SM-SLM. See the
Diagnostics
section in the
SM-SLM User Guide
for more information.
SLX.HF
Solutions Module slot X trip: Solutions Module X hardware fault
200,205,210
Ensure Solutions Module is installed correctly
Return Solutions Module to supplier
SLX.nF
Solutions Module slot X trip: Solutions Module has been removed
203,208,213
Ensure Solutions Module is installed correctly
Reinstall Solutions Module
Save parameters and reset drive
SL.rtd
Solutions Module trip: Drive mode has changed and Solutions Module parameter routing is now incorrect
215
Press reset.
If the trip persists, contact the supplier of the drive.
SLX.tO
Solutions Module slot X trip: Solutions Module watchdog timeout
201,206,211
Press reset.
If the trip persists, contact the supplier of the drive.
t038
User defined trip
38
Onboard PLC and/or SM-Applications program must be interrogated to find the cause of this trip
t040 to t089
User defined trip
40 to 89
Onboard PLC and/or SM-Applications program must be interrogated to find the cause of this trip
t099
User defined trip
99
Onboard PLC and/or SM-Applications program must be interrogated to find the cause of this trip
t101
User defined trip
101
Onboard PLC and/or SM-Applications program must be interrogated to find the cause of this trip
t112 to t160
User defined trip
112 to 160
Onboard PLC and/or SM-Applications program must be interrogated to find the cause of this trip
t168 to t174
User defined trip
168 to 174
Onboard PLC and/or SM-Applications program must be interrogated to find the cause of this trip
Trip
Diagnosis
Error Code
Trip Description
0
No fault detected
1
Power supply overloaded
2
SLM version is too low
3
DriveLink error
4
Incorrect switching frequency selected
5
Feedback source selection incorrect
6
Encoder error
7
Motor object number of instances error
8
Motor object list version error
9
Performance object number of instances error
10
Parameter channel error
11
Drive operating mode incompatible
12
Error writing to the SLM EEPROM
13
Motor object type incorrect
14
Unidrive SP object error
15
Encoder object CRC error
16
Motor object CRC error
17
Performance object CRC error
18
Unidrive SP object CRC error
19
Sequencer timeout
74
Solutions module over temperature