User Manual
Chapter 3
GFK-1742F
Jan 2020
Installing and Wiring the DSM314
85
Circuit
Identifier
Servo Axis 1-4
Circuit
Function
Aux Axis 2-4
Circuit
Function
Signal Name
(X = A, B, C, or
D Connector)
Faceplate
Pin
Auxiliary
Terminal
Board
Servo
Terminal
Board
IN9
Overtravel (+)
Faceplate 24v
Input
IN9_X
16
16
6
IN10
Overtravel (-)
Faceplate 24v
Input
IN10_X
34
34
14
IN11
Home Switch
Home Switch
IN11_X
17
17
7
INCOM
24v Input
Common
24v Input
Common
INCOM_X
35
35
15
I/O Type:
Optically Isolated 24v Source / Sink Inputs
Circuit Type:
Source / Sink (5K resistance to INCOM)
Input Impedance:
5.4K ohms to INCOM (@ 24 VDC)
Maximum Input Voltage:
+/- 30.0v (referenced to INCOM)
Logic 0 Threshold:
+/- 6.0 v max (referenced to INCOM)
Logic 1 Threshold:
+/- 18.0 v min (referenced to INCOM)
Input Filtering:
5 milliseconds typical
Note:
These inputs use bi-directional optocouplers and can be turned on with either a positive or
negative input with respect to INCOM.