User Manual
Chapter 4
GFK-1742F
Jan 2020
Configuration
97
Figure 59
This operation adds the DSM314 to the rack and displays the DSM314 configuration screens
that allow you to customize the DSM314 to your application. Refer to chapter 4 for details
concerning the DSM314 configuration settings.
You should complete the configuration of your host controller to include the Power Supply,
Rack, CPU and additional modules to match the target system. Consult the software
user’s manual and on
-line help as needed.
Important
The completed configuration must be stored to the host contro
ller. See “Storing Your
Configuration to the PLC” in Chapter 2 for instructions on how to
do this. For additional
details, consult the software user’s manual, and on
-line help.
Note:
A host controller status error of “System Configuration Mismatch” with th
e same rack/slot
location as a DSM314 indicates that there is a parameter configured and sent to the DSM314 that
has been rejected by the DSM314. Carefully check each parameter of your DSM314 configuration
with the configuration settings in this manual for the discrepancy. Correct the discrepancy, clear
the host controller Fault, and re-Store the configuration. Check that the error has been corrected.
See the next section, Enabling Run Mode on the PLC, for instructions on viewing and clearing PLC
faults.
The DSM314 can detect many typical configuration errors. These are returned as error codes of
the form Dxxx (hex) in the Module Status Code %AI word or Axis Error Code %AI words. These errors
do not cause a host controller status of “System Configuration Mismatch”. Refer to Appendix A
for a description of these errors. Correct any configuration errors and restore the configuration
with the host controller in Stop mode.
4.3
Module Configuration