User Manual
Appendix H
GFK-1742F
Jan 2020
Using VersaPro with the DSM314
492
One method to rename the profile is to right-click the profile name in the Navigator window
and choose Rename Profile (Figure 254) from the short-cut menu. Type a name for the
profile and press ENTER to finish. The profile and any CAM profile links to it are renamed.
For this example, the profile is renamed to ExCamProfile. Refer to the on-line help for
additional information.
Figure 254: Rename Profile
Step 4: Link the CAM Profile to the CAM Block
•
CAM Profiles must be linked to their associated CAM block. A CAM block can contain
numerous CAM profiles. The DSM has two limits that affect the number of profiles.
The maximum CAM block size is 50K, and the maximum number of linked profiles
for an individual block is 100. The CAM Profile library is only limited by available disk
space on the host computer. The CAM block is linked to the DSM via the CAM Block
entry in Hardware configuration.
Although there is more than one way to link a CAM profile to a CAM block, the easiest
method is simply to drag and drop the desired CAM profile onto the applicable CAM
block. The result is shown in the next figure.
Note:
VersaPro limits the download block total size (Motion, Local Logic, and CAM combined) to 32K.