User Manual
Chapter 3
GFK-1742F
Jan 2020
Installing and Wiring the DSM314
92
+5v Power
Circuit
Identifier
Servo Axis
Circuit
Function
Aux Axis
Circuit
Function
Signal Name
(X = A, B, C, or
D Connector)
Faceplate
Pin
Auxiliary
Terminal
Board
Servo
Terminal
Board
P5V
5v Power
5v Power
P5V_X
4
4
3
0V
0v
0v
0V_X
22
22
11
I/O Type:
+5V Encoder Power
Circuit Type:
+5V Power with Electronic Short Circuit Protection
Output Voltage:
4.70 v to 5.20 v at 0.5 amp
Output Current:
0.5 amp max (total for all connectors)
Notes:
Note:
This output is intended to power external devices such as Incremental Quadrature Encoders
requiring less than 0.5 amps total from all four axis connectors. The output current is provided by
the host controller bac5v supply and is protected by an electronic short circuit protector
in the DSM314 module.
The total external device current drawn from this +5V circuit must be added to the power supply
consumption value in the DSM314 configuration screen in the configuration software and must
be added in if performing a manual power supply loading calculation.
The listed 0v pin should normally be used as the power return signal.