User Manual
Chapter 2
GFK-1742F
Jan 2020
System Overview
45
After configuring the communications port, the local logic program can be downloaded
(stored) to the Host Controller CPU. To store the current folder to the Host Controller,
choose Target from the Menu Bar and Go Online with “<Target>” from the submenu.
Once
connected, choose Target from the Menu Bar and Download “<Target>” to PLC from the
submenu. The store operation begins the folder transfer process from the programmer to
the Host Controller CPU. When you initiate the store operation, a dialog box is presented
that allows you to choose what to store to the Host Controller. To store the hardware
configuration, select Hardware configuration and Motion.
Note:
Local Logic and Motion programs are transferred with the Hardware Configuration.
Figure 30: Machine Edition Download Dialog Box
Machine Edition will indicate any errors or that it has successfully downloaded the program
in the Feedback Zone window.
Note:
A host controller status error of “System Configuration Mismatch” with the same rack/slot
location as a DSM314 indicates that there is a parameter configured and sent to the DSM314 that
has been rejected by the DSM314. Carefully check each parameter of your DSM314 configuration
with the configuration settings in this manual for the discrepancy. Correct the discrepancy, clear
the host controller Fault, and re-Store the configuration. Check that the error has been corrected.
See the next section, Enabling Run Mode on the PLC, for instructions on viewing and clearing PLC
faults.
The DSM314 can detect many typical configuration errors. These are returned as error codes of
the form Dxxx (hex) in the Module Status Code %AI word or Axis Error Code %AI words. These errors
do not cause a host controller status of “System Configuration Mismatch”. Refer to Appendix A
for a description of these errors. Correct any configuration errors and restore the configuration
with the host controller in Stop mode.