Flame Operation Faults
105
Flame detected out of sequence
1. Check that flame is not present in the combustion
chamber. Correct any errors.
2. Make sure that the flame detector is wired to the correct
terminal.
3. Make sure the F & G wires are protected from stray
noise pickup.
4. Reset and sequence the module, if code reappears,
replace the flame detector.
5. Reset and sequence the module, if code reappears,
replace the module.
H or L
106
Flame lost in MFEP
1. Check pilot valve (Main Valve for DSI) wiring and
operation - correct any errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, flame detector,
flame detector siting or flame rod position.
5. If steps 1 through 4 are correct and the fault persists,
replace the module.
L
107
Flame lost early in run
L
108
Flame lost in run
L
109
Ignition failed
L
110
Ignition failure occurred
Hold time of recycle and hold option. Will not be a lockout
fault. Hold Only.
H
111
Flame current lower than WEAK threshold
Internal hardware test. Not a lockout,
H
112
Pilot test flame timeout
Interrupted Pilot or DSI application and flame lost when
system in “test” mode.
1. Reset the module to restart.
L
113
Flame circuit timeout
Flame sensed during Initiate or off cycle, hold 240
seconds, if present after 240 seconds, lockout.
L
114-121
RESERVED
Rate Proving Faults
122
Lightoff rate proving failed
1. Check wiring and correct any potential wiring errors.
2. Check VFDs ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.
L
123
Purge rate proving failed
L
124
High fire switch OFF
1. Check wiring and correct any potential wiring errors.
2. Check High Fire Switch to assure proper function (not
welded or jumpered).
3. Manually drive the motor to the High Fire position and
adjust the HF switch while in this position and verify
voltage through the switch to the HFS input with a
voltmeter.
4. If steps 1-3 are correct and the fault persists, replace the
module.
H
125
High fire switch stuck ON
H
126
Low fire switch OFF
1. Check wiring and correct any potential wiring errors.
2. Check Low Fire Switch to assure proper function (not
welded or jumpered).
3. Manually drive the motor to the High Fire position and
adjust the LF switch while in this position and verify voltage
through the switch to the LFS input with a voltmeter.
4. If steps 1-3 are correct and the fault persists, replace the
module.
H
127
Low fire switch stuck ON
H or L
128
Fan speed failed during prepurge
1. Check wiring and correct any potential wiring errors.
2. Check VFDs ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.
H or L
129
Fan speed failed during preignition
H or L
130
Fan speed failed during ignition
H or L
131
Fan movement detected during standby
H
132
Fan speed failed during run
H
133-135
RESERVED
Start Check Faults
Table 49. Falcon Lockout and Hold Codes. (Continued)
Code
Description
Recommended Troubleshooting of Lockout Codes
NOTE
Summary of Contents for CFC-1000
Page 35: ...Section 2 Installation Part No 750 263 2 21 Figure 2 23 Gas Piping ...
Page 47: ...Section 2 Installation Part No 750 263 2 33 Figure 2 41 Electrical Connection Diagram ...
Page 49: ...Section 2 Installation Part No 750 263 2 35 Figure 2 43 CFC Wiring Diagram dual fuel units ...
Page 50: ...Section 2 Installation 2 36 Part No 750 263 ...
Page 70: ...Section 3 Stack and Intake Vent Sizing and Installation 3 20 Part No 750 263 ...
Page 102: ...Section 4 CFC Commissioning 4 32 Part No 750 263 ...
Page 108: ...Section 5 Service and Maintenance 5 6 Part No 750 263 ...
Page 113: ...Section 6 Parts Part No 750 263 6 5 Figure 6 3 Casing Table 6 5 Casing parts ...
Page 117: ...Section 6 Parts Part No 750 263 6 9 Figure 6 7 Electrical assemblies single fuel ...
Page 123: ...APPENDIX A CB FALCON CONTROLLER ...
Page 124: ......
Page 244: ...CB FALCON 750 265 120 ...
Page 245: ...APPENDIX B CB FALCON PLUG IN MODULE ...
Page 246: ......
Page 250: ......
Page 251: ...APPENDIX C GAS VALVE ...
Page 252: ......
Page 269: ...APPENDIX D CB FALCON MODBUS COMMUNICATION ...
Page 270: ......