Slow Start and Forced Rate limits (Hydronic Control)
The Forced Rate limit causes the burner to stay at a fixed firing rate immediately after lightoff, just after the end of the Run
Stabilization time (if any). This is optionally followed by a slow start function that limits the ramp-up speed of the firing rate when the
water is colder than a threshold, as shown in the following diagram.
Fig. 20. Slow Start and Forced Rate limits.
Table 23. Limits and Rate Override: Slow Start Limit Parameters.
Parameter
Comment
CH forced rate time
MM:SS
This parameter determines the duration of the forced rate period, when firing for CH or LL
demand. If it is set to zero then this forced rate period is disabled.
CH forced rate
RPM or %
This parameter provides the firing rate during the CH forced rate time. It is also the initial rate
for the CH slow start period (even if the forced rate time is zero).
DHW forced rate time
MM:SS
This parameter determines the duration of the forced rate period, when firing for DHW
demand. If it is set to zero then this forced rate period is disabled.
DHW forced rate
RPM or %
This parameter provides the firing rate during the DHW forced rate time. It is also the initial
rate for the DHW slow start period (even if the DHW forced rate time is zero).
PFEP/MFEP/DBI
RUN STAB.
FORCED RATE
SLOW START
MODULATION
ENDS WHEN OUTLET
TEMP EXCEEDS
OPERATING
SETPOINT
MINUS
TURN-OFF ADJUSTMENT
STARTS WHEN FREE
MODULATION BEGINS.
(0 = DISABLE)
SETPOINT = OFF HYST.
SETPOINT - OFF HYST.
A PROGRAMMABLE PARAMETER
A PROGRAMMABLE PARAMETER THAT IS NOT
PART OF FORCED RATE OR SLOW START
=
=
FORCED RATE AND SLOW START
SETPOINT - SLOWSTART DEGREES
OUTLET
TEMPERATURE
SETPOINT
(0 = DISABLE)
IGNITION
RUN
LIGHTOFF RATE
TIME
NAME
NAME
DEGREES
CH FORCED RATE
SLOW START DEGREES
DHW FORCED RATE
CH TIME
DHW TIME
CH ENABLE
DHW ENABLE
RAMP
(THIS THRESHOLD ALSO COULD BE HIGHER
THAN THE BURNER-ON THRESHOLD, IF THE
SLOWSTART DEGREES VALUE WAS SMALLER
THAN THE ON HYSTERESIS VALUE.)
Summary of Contents for CFC-1000
Page 35: ...Section 2 Installation Part No 750 263 2 21 Figure 2 23 Gas Piping ...
Page 47: ...Section 2 Installation Part No 750 263 2 33 Figure 2 41 Electrical Connection Diagram ...
Page 49: ...Section 2 Installation Part No 750 263 2 35 Figure 2 43 CFC Wiring Diagram dual fuel units ...
Page 50: ...Section 2 Installation 2 36 Part No 750 263 ...
Page 70: ...Section 3 Stack and Intake Vent Sizing and Installation 3 20 Part No 750 263 ...
Page 102: ...Section 4 CFC Commissioning 4 32 Part No 750 263 ...
Page 108: ...Section 5 Service and Maintenance 5 6 Part No 750 263 ...
Page 113: ...Section 6 Parts Part No 750 263 6 5 Figure 6 3 Casing Table 6 5 Casing parts ...
Page 117: ...Section 6 Parts Part No 750 263 6 9 Figure 6 7 Electrical assemblies single fuel ...
Page 123: ...APPENDIX A CB FALCON CONTROLLER ...
Page 124: ......
Page 244: ...CB FALCON 750 265 120 ...
Page 245: ...APPENDIX B CB FALCON PLUG IN MODULE ...
Page 246: ......
Page 250: ......
Page 251: ...APPENDIX C GAS VALVE ...
Page 252: ......
Page 269: ...APPENDIX D CB FALCON MODBUS COMMUNICATION ...
Page 270: ......