CB FALCON MODBUS COMMUNICATION
7
Table 4. CB Falcon Modbus register map
0024
0036
Annunciator first out
R
U16
Source for annunciator first out:
0=None or undetermined,
1=ILK,
2=PII,
11=Annunciator 1,
12=Annunciator 2,
13=Annunciator 3,
14=Annunciator 4,
15=Annunciator 5,
16=Annunciator 6,
17=Annunciator 7,
18=Annunciator 8
0025
0037
Annunciator hold
R
U16
Source for burner control hold condition (see Hold code):
0=None or undetermined,
1=ILK,
2=PII,
3=LCI
11=Annunciator 1,
12=Annunciator 2,
13=Annunciator 3,
14=Annunciator 4,
15=Annunciator 5,
16=Annunciator 6,
17=Annunciator 7,
18=Annunciator 8
0026
0038
Sequence time
R
U16
Running time for timed burner control operation
(seconds)
0027
0039
Delay time
R
U16
Running delay time (seconds). Applicable when burner
control in delayed or hold state.
0028
0040
Hold code
R
U16
Reason for burner hold (same codes as lockout, see
table 7)
0029
0041
Burner control flags
R
U16
Bit map:
15-1=Reserved (always 0)
0= Flame detected
002A
0042
Remote Stat
R/W
U16
0=No remote STAT demand,
1=remote STAT demand indicated
SENSOR STATUS
002B
0043
Outlet operation (S4=J8-10)
terminal
R
U16
-40°-130° (0.1°C precision)
d
or other (see register 610)
002C
0044
DHW operation (S7=J9-3)
terminal
R
U16
-40°-130° (0.1°C precision)
e
or other (see register 612)
002D
0045
Stack or Heat exchanger
operation (S9=J9-6)
terminal
R
U16
-40°-130° (0.1°C precision)
e
or other (see register 613)
002E
0046
Outlet operation sensor
(S4=J8-10) state
R
U16
0=None, 1=Normal, 2=Open, 3=Shorted, 4=Outside high
range, 5=Outside low range, 6=Not reliable
002F
0047
DHW operation sensor
(S7=J9-3) state
R
U16
0=None, 1= Normal, 2=Open, 3=Shorted, 4=Outside
high range, 5=Outside low range, 6=Not reliable
0030
0048
Outlet limit sensor (S3=J8-8)
state
R
U16
0=None, 1=Normal, 2=Open, 3=Shorted, 4=Outside high
range, 5=Outside low range, 6=Not reliable
0031
0049
Inlet sensor (S1=J8-4) state R
U16
0=None, 1= Normal, 2=Open, 3=Shorted, 4=Outside
high range, 5=Outside low range, 6=Not reliable
0032
0050
DHW limit sensor (S7=J9-1)
state
R
U16
0=None, 1= Normal, 2=Open, 3=Shorted, 4=Outside
high range, 5=Outside low range, 6=Not reliable
0033
0051
Stack limit sensor (S8=J9-4)
state
R
U16
0=None, 1= Normal, 2=Open, 3=Shorted, 4=Outside
high range, 5=Outside low range, 6=Not reliable
0034
0052
S5 (J8-11) sensor state
R
U16
0=None, 1= Normal, 2=Open, 3=Shorted, 4=Outside
high range, 5=Outside low range, 6=Not reliable
Summary of Contents for CFC-1000
Page 35: ...Section 2 Installation Part No 750 263 2 21 Figure 2 23 Gas Piping ...
Page 47: ...Section 2 Installation Part No 750 263 2 33 Figure 2 41 Electrical Connection Diagram ...
Page 49: ...Section 2 Installation Part No 750 263 2 35 Figure 2 43 CFC Wiring Diagram dual fuel units ...
Page 50: ...Section 2 Installation 2 36 Part No 750 263 ...
Page 70: ...Section 3 Stack and Intake Vent Sizing and Installation 3 20 Part No 750 263 ...
Page 102: ...Section 4 CFC Commissioning 4 32 Part No 750 263 ...
Page 108: ...Section 5 Service and Maintenance 5 6 Part No 750 263 ...
Page 113: ...Section 6 Parts Part No 750 263 6 5 Figure 6 3 Casing Table 6 5 Casing parts ...
Page 117: ...Section 6 Parts Part No 750 263 6 9 Figure 6 7 Electrical assemblies single fuel ...
Page 123: ...APPENDIX A CB FALCON CONTROLLER ...
Page 124: ......
Page 244: ...CB FALCON 750 265 120 ...
Page 245: ...APPENDIX B CB FALCON PLUG IN MODULE ...
Page 246: ......
Page 250: ......
Page 251: ...APPENDIX C GAS VALVE ...
Page 252: ......
Page 269: ...APPENDIX D CB FALCON MODBUS COMMUNICATION ...
Page 270: ......