Table 7. General Configuration Settings.
Parameter
Comment
Temperature Units
F, C
This parameter determines whether the temperature is represented in units of Fahrenheit or Celsius
degrees.
Anti short cycle time
mm:ss
Whenever the burner is turned off due to no demand, the anti short cycle timer is started and the
burner remains in a Standby Delay condition waiting for this time to expire. The anti short cycle time
does not apply, however, to recycle events such as loss of airflow or flame, it applies only to loss of
demand.
The anti short cycle time always inhibits a CH or LL demand. However, if a DHW demand occurs
then its priority is checked. If it has the highest priority because of either:
•
a non-zero value in the DHW priority timer (which is loaded using the DHW priority time
parameter)
•
due to the setting in both: DHW priority vs LL (if Lead Lag Master enable is enabled) AND DHW
priority vs CH (if CH enable is enabled)
•
then the anti short cycle delay is ignored and the DHW demand is served.
Burner name
text
The Burner Name is a text parameter stored in the Falcon to identify the burner.
OEM ID
text
The OEM ID is a text parameter stored in the Falcon intended for use by an OEM to record
identification information related to the OEM's configuration and setup of the Falcon.
Installation Data
text
The Installation Data is a text parameter stored in the Falcon. It is intended for use by the installer to
record identification information about how the Falcon was set up at the installation time.
Summary of Contents for CFC-1000
Page 35: ...Section 2 Installation Part No 750 263 2 21 Figure 2 23 Gas Piping ...
Page 47: ...Section 2 Installation Part No 750 263 2 33 Figure 2 41 Electrical Connection Diagram ...
Page 49: ...Section 2 Installation Part No 750 263 2 35 Figure 2 43 CFC Wiring Diagram dual fuel units ...
Page 50: ...Section 2 Installation 2 36 Part No 750 263 ...
Page 70: ...Section 3 Stack and Intake Vent Sizing and Installation 3 20 Part No 750 263 ...
Page 102: ...Section 4 CFC Commissioning 4 32 Part No 750 263 ...
Page 108: ...Section 5 Service and Maintenance 5 6 Part No 750 263 ...
Page 113: ...Section 6 Parts Part No 750 263 6 5 Figure 6 3 Casing Table 6 5 Casing parts ...
Page 117: ...Section 6 Parts Part No 750 263 6 9 Figure 6 7 Electrical assemblies single fuel ...
Page 123: ...APPENDIX A CB FALCON CONTROLLER ...
Page 124: ......
Page 244: ...CB FALCON 750 265 120 ...
Page 245: ...APPENDIX B CB FALCON PLUG IN MODULE ...
Page 246: ......
Page 250: ......
Page 251: ...APPENDIX C GAS VALVE ...
Page 252: ......
Page 269: ...APPENDIX D CB FALCON MODBUS COMMUNICATION ...
Page 270: ......