Section 4 — CFC Commissioning
Part No. 750-263
4-13
Anti-condensation Configuration
CH anti-condensation pump
force off
Service
Disabled
0498
Anti-condensation Configuration
DHW anti-condensation
enable
Service
Disabled
0499
Anti-condensation Configuration
DHW anti-condensation
setpoint
Service
32
140
194
°F
0500
Anti-condensation Configuration
DHW anti-condensation
pump force off
Service
Disabled
0501
Anti-condensation Configuration
Anti-condensation > Outlet
limit
Service
No
0502
Anti-condensation Configuration Anti-condensation > Delta-T
Service
No
0502
Anti-condensation Configuration
Anti-condensation > Stack
limit
Service
No
0502
Anti-condensation Configuration
Anti-condensation > Slow
start
Service
Yes
0502
Anti-condensation Configuration
Anti-condensation > Forced
rate
Service
Yes
0502
Anti-condensation Configuration
Frost protect
anticondensation enable
Service
No
0503
Frost Protection Configuration
CH frost protection enable
Service
Disabled
0528
Frost Protection Configuration
DHW frost protection enable
Service
Disabled
0529
Frost Protection Configuration
Outdoor frost protection
setpoint
Service
-40
32
120
°F
0530
Frost Protection Configuration
LL frost protection enable
Service
Disabled
0532
Frost Protection Configuration
LL frost protection rate
Service
0
20%
100
0533
Lead Lag Configuration
Lead Lag slave enable
Service
Disabled
0544
Lead Lag Configuration
Lead Lag master enable
Service
Disabled
0545
Lead Lag Configuration
Lead Lag CH setpoint
Service
32
150
230
°F
0546
Lead Lag Configuration
Lead Lag CH TOD setpoint
Service
32
120
230
°F
0547
Lead Lag Configuration
Lead Lag on hysteresis
Service
5
°F
0549
Lead Lag Configuration
Lead Lag off hysteresis
Service
15
°F
0550
Lead Lag Configuration
Lead Lag hysteresis step
time
Service
60
seconds
0551
Lead Lag Configuration
Lead Lag P gain
Service
0
10
400
0552
Lead Lag Configuration
Lead Lag I gain
Service
0
25
400
0553
Lead Lag Configuration
Lead Lag D gain
Service
0
0
400
0554
Lead Lag Configuration
Lead Lag operation switch
Service
Yes/True/On
0555
Lead Lag Configuration
Lead Lag CH demand switch
Service
STAT terminal
0556
Lead Lag Configuration
Lead Lag CH setpoint source
Service
Local
0557
Lead Lag Configuration
Lead Lag modulation backup
sensor
Service
Use average of all
slave outlet sensors
0559
Lead Lag Configuration
Lead Lag CH 4mA water
temperature
Service
80
°F
0560
Lead Lag Configuration
Lead Lag CH 20mA water
temperature
Service
180
°F
0561
Lead Lag Configuration
Slave mode
Service
Equalize run time
0564
Lead Lag Configuration
Base load rate
Service
800
2000
6000
RPM
0566
Lead Lag Configuration
Fan rate during off cycle
Service
0
0
6000
RPM
0567
Lead Lag Configuration
Slave sequence order
Service
0
0568
Lead Lag Configuration
Lead Lag Modbus port
Service
MB2
0569
Lead Lag Configuration
Lead Lag slave demand to
firing delay
Service
60
300
seconds
0570
Lead Lag Configuration
Base load common
Service
0
45%
100
%
0572
Lead Lag Configuration
Lead selection method
Service
Lowest measured run
time
0574
Lead Lag Configuration
Lag selection method
Service
Rotate in sequence
order
0575
Lead Lag Configuration
Lead Lag add stage method
1
Service
Firing rate threshold
0714
Table 4-1 CFC default parameter settings
Parameter Group
Parameter Name
Access*
Min.
Range
Default Setting
Max.
Range
Parameter
Units
Installation Setting
Modbus
Register
(dec)
Summary of Contents for CFC-1000
Page 35: ...Section 2 Installation Part No 750 263 2 21 Figure 2 23 Gas Piping ...
Page 47: ...Section 2 Installation Part No 750 263 2 33 Figure 2 41 Electrical Connection Diagram ...
Page 49: ...Section 2 Installation Part No 750 263 2 35 Figure 2 43 CFC Wiring Diagram dual fuel units ...
Page 50: ...Section 2 Installation 2 36 Part No 750 263 ...
Page 70: ...Section 3 Stack and Intake Vent Sizing and Installation 3 20 Part No 750 263 ...
Page 102: ...Section 4 CFC Commissioning 4 32 Part No 750 263 ...
Page 108: ...Section 5 Service and Maintenance 5 6 Part No 750 263 ...
Page 113: ...Section 6 Parts Part No 750 263 6 5 Figure 6 3 Casing Table 6 5 Casing parts ...
Page 117: ...Section 6 Parts Part No 750 263 6 9 Figure 6 7 Electrical assemblies single fuel ...
Page 123: ...APPENDIX A CB FALCON CONTROLLER ...
Page 124: ......
Page 244: ...CB FALCON 750 265 120 ...
Page 245: ...APPENDIX B CB FALCON PLUG IN MODULE ...
Page 246: ......
Page 250: ......
Page 251: ...APPENDIX C GAS VALVE ...
Page 252: ......
Page 269: ...APPENDIX D CB FALCON MODBUS COMMUNICATION ...
Page 270: ......