CB FALCON MODBUS COMMUNICATION
28
Table 4. CB Falcon Modbus register map
02C9
0713
Slave dropout/return
compensation
R/W
U16
0=No slave compensation,
1=Replace dropout immediately,
2=Adjust rate for remaining slaves,
3=Both replace dropout & adjust rate
02CA
0714
Add stage method
R/W
U16
0=Do not add stage,
1=Use error threshold,
2=Use firing rate threshold,
3=Use error rate change & threshold,
4=Use firing rate change & threshold
02CB
0715
RESERVED
02CC
0716
Add stage detection time
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
02CD
0717
RESERVED
02CE
0718
Add stage error threshold
R/W
U16
0°-130° (0.1°C precision)
a
02CF
0719
Add stage rate offset
R/W
U16
-100-100%
2
(0.1% units)
02D0
0720
Add stage error gain
R/W
U16
0-100
02D1
0721
Add stage rate gain
R/W
U16
0-100
02D2
0722
Add stage inter-stage delay R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
02D3
0723
Drop stage method
R/W
U16
0=Do not drop stage,
1=Use error threshold,
2=Use firing rate threshold,
3=Use error rate change & threshold,
4=Use firing rate change & threshold
02D4
0724
RESERVED
02D5
0725
Drop stage detection time
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
02D6
0726
RESERVED
02D7
0727
Drop stage error threshold
R/W
U16
0°-130° (0.1°C precision)
a
02D8
0728
Drop stage rate offset
R/W
U16
-100-100%
2
(0.1% units)
02D9
0729
Drop stage error gain
R/W
U16
0-100
02DA
0730
Drop stage rate gain
R/W
U16
0-100
02DB
0731
Drop stage inter-stage delay R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
02DC
0732
RESERVED
02DD
0733
Lead rotation time
R/W
U16
0-64800 minutes (1080 hours), 0xFFFF=Not configured
02DE
0734
Force lead rotation time
R/W
U16
0-64800 minutes (1080 hours), 0xFFFF=Not configured
02DF-02EF
0735-0751
RESERVED
EXTENDED PUMP
CONFIGURATION
02F0
0752
Auxiliary 1 pump overrun
time
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
02F1
0753
Auxiliary 1 pump options 1
R/W
U16
Bit map:
15=Normal pump demand when auxiliary pump Z is set,
14=Normal pump demand when auxiliary pump Y is set,
13=Normal pump demand when auxiliary pump X is set,
12-7=Reserved (always 0),
6=Normal pump demand when DHW service is active,
5=Normal pump demand when CH service is active,
4=Reserved,
3=Normal pump demand when DHW demand,
2=Normal pump demand when CH demand,
1=Normal pump demand when local burner demand,
0=Local demand inhibited for faults
Summary of Contents for CFC-1000
Page 35: ...Section 2 Installation Part No 750 263 2 21 Figure 2 23 Gas Piping ...
Page 47: ...Section 2 Installation Part No 750 263 2 33 Figure 2 41 Electrical Connection Diagram ...
Page 49: ...Section 2 Installation Part No 750 263 2 35 Figure 2 43 CFC Wiring Diagram dual fuel units ...
Page 50: ...Section 2 Installation 2 36 Part No 750 263 ...
Page 70: ...Section 3 Stack and Intake Vent Sizing and Installation 3 20 Part No 750 263 ...
Page 102: ...Section 4 CFC Commissioning 4 32 Part No 750 263 ...
Page 108: ...Section 5 Service and Maintenance 5 6 Part No 750 263 ...
Page 113: ...Section 6 Parts Part No 750 263 6 5 Figure 6 3 Casing Table 6 5 Casing parts ...
Page 117: ...Section 6 Parts Part No 750 263 6 9 Figure 6 7 Electrical assemblies single fuel ...
Page 123: ...APPENDIX A CB FALCON CONTROLLER ...
Page 124: ......
Page 244: ...CB FALCON 750 265 120 ...
Page 245: ...APPENDIX B CB FALCON PLUG IN MODULE ...
Page 246: ......
Page 250: ......
Page 251: ...APPENDIX C GAS VALVE ...
Page 252: ......
Page 269: ...APPENDIX D CB FALCON MODBUS COMMUNICATION ...
Page 270: ......