CB FALCON
99
750-265
Tap detect on
hysteresis
The second tap demand “set” criteria depends on the value of the DHW sensor. If the
temperature is less than or equal to the threshold given by subtracting this parameter from
the normal DHW setpoint, and if this condition has persisted for the time specified by the
Tap detect recognition time parameter, the Tap demand block is “Set” (Tap demand
becomes true and the minimum on timer is started).
36
Tap detect on
recognition time
This parameter provides the time for a Tap detect event due to the Tap detect on hysteresis
parameter, as described just above.
36
Tap stop Inlet-DHW
degrees
One criteria for asserting “Clr” is based on the difference between the DHW and the Inlet
temperature, calculated as: Inlet - DHW. When this value is positive and is greater than or
equal to the degrees given by this parameter, tap demand’s “Clr” input is asserted.
37
Tap stop Outlet-Inlet
degrees
The other criteria for asserting “Clr” is based on the difference between the Outlet and the
Inlet temperature, calculated as: Outlet - Inlet. When this value is negative or is less than or
equal to the degrees given by this parameter, tap demand’s “Clr” input is asserted.
37
Temperature units
This parameter determines whether temperature is represented in units of Fahrenheit or
Celsius degrees.
21
Warm Weather
Shutdown
Enable, Disable, Shutdown after demands have ended, Shutdown immediately
19
Warm Weather
Shutdown Setpoint
Temperature, None
20
XX pump output
This allows the XX pump function to be disconnected or to be attached to any of the pump
outputs.
If two pump blocks are connected to the same pump output then their signals are effectively
OR'd together as shown in Fig. 22.
54
XX pump control
The XX pump can be turned on manually, or it can be set to operate automatically. If it is
turned on then it remains on until changed back to Auto.
54
XX pump start delay When the pump demand changes from off to on, this delay time is used to delay the start of
the pump. The pump then starts after the delay expires, assuming that the demand is still
present.
A delay time of zero disables the delay.
For a stand-alone (non-slave) Falcon, this delay is skipped and does not occur if it is
already firing when the pump demand off-to-on event occurs.
For a Falcon in slave mode, this delay is skipped and does not occur if the “Master Service
Status” (defined in the LL specification and noted in the drawing) informs the slave unit that
some slave burner in the system is already firing, when the pump demand off-to-on event
occurs.
55
XX pump overrun
time
This time indicates how long the pump should remain on after pump demand ends.
A time of zero disables the overrun.
However, a pump should overrun to use up the last of the heat only if it is the last pump
running.
Therefore: For a stand-alone Falcon if any local service is active then this status cancels
any overrun that is in-progress.
For a slave Falcon if any master service is active at this time this status cancels any overrun
that is in-progress.
55
XX pump cycles
The XX pump cycle counters are mapped to the physical cycle counters; there is one
counter for each of the three physical pump outputs and this counter is visible via this
parameter, for whichever pump block (or blocks) are connected to it via the block's XX
pump output parameter. It is possible for two (or more) pump functions to be assigned to the
same physical pump. In this case, that physical pump's cycle counter is visible in each
pump control block. A pump cycle counter has the range 0 through 999,999 and it can be
restarted if a pump is replaced.
55
Table 47. Parameter Glossary.
Parameter Name
Short Description
Ref. Page
Summary of Contents for CFC-1000
Page 35: ...Section 2 Installation Part No 750 263 2 21 Figure 2 23 Gas Piping ...
Page 47: ...Section 2 Installation Part No 750 263 2 33 Figure 2 41 Electrical Connection Diagram ...
Page 49: ...Section 2 Installation Part No 750 263 2 35 Figure 2 43 CFC Wiring Diagram dual fuel units ...
Page 50: ...Section 2 Installation 2 36 Part No 750 263 ...
Page 70: ...Section 3 Stack and Intake Vent Sizing and Installation 3 20 Part No 750 263 ...
Page 102: ...Section 4 CFC Commissioning 4 32 Part No 750 263 ...
Page 108: ...Section 5 Service and Maintenance 5 6 Part No 750 263 ...
Page 113: ...Section 6 Parts Part No 750 263 6 5 Figure 6 3 Casing Table 6 5 Casing parts ...
Page 117: ...Section 6 Parts Part No 750 263 6 9 Figure 6 7 Electrical assemblies single fuel ...
Page 123: ...APPENDIX A CB FALCON CONTROLLER ...
Page 124: ......
Page 244: ...CB FALCON 750 265 120 ...
Page 245: ...APPENDIX B CB FALCON PLUG IN MODULE ...
Page 246: ......
Page 250: ......
Page 251: ...APPENDIX C GAS VALVE ...
Page 252: ......
Page 269: ...APPENDIX D CB FALCON MODBUS COMMUNICATION ...
Page 270: ......