CB FALCON
23
750-265
Fig. 5. Demand and rate selection diagram.
The demand priority control block shown in Fig. 5 determines
which source of demand has control of the burner, according to
parameters and the logic described below.
The DHW priority timer within this block operates according to
the logic:
Fig. 6. DHW priority timer logic.
ANTI-CONDENS...
BOOST:
“mRATE” = ANALOG% OR RPM
PARAMETER
SENSOR
“pRATE” = 0 TO 99.99% OF CAPACITY
INPUT
OUTPUT
TERMINALS
DELTA-T ...
STACK LIMIT ...
SLOW START ...
REDUCE:
ANTI-CONDENSATION
PRIORITY
STACK
CH BURNER DEMAND
DHW BURNER DEMAND
LL SLAVE DEMAND
BURNER DEMAND
BURNER DEMAND
BURNER STATUS
COMMANDED RATE
ANALOG PERCENTAGE
OUTPUT
MIN/MAX FAN
SPEED LIMIT
MIN PWM
LIMIT
MIN. MOD. RATE
MAX. MOD. RATE
ABS. MIN. RATE
ABS. MAX. RATE
FAN SPEED
RAMP
CH RATE
DHW RATE
LL SLAVE RATE
RATE LIMITS
RATE OVERRIDE
OVERRIDE
LIMITS
FIRING RATE
PWM
4-20mA
0-10V
INLET
OUTLET
FROST BURNER DEMAND
FROST PROTECTION RATE
DEMAND
PRIORITY
CONTROL
DHW ENABLE
CH ENABLE
PRIORITY: CH <>DWH LL<>DHW
pRATE TO mRATE
CONVERSION
TOP: FIRING & BC HAS NO COMMANDED RATE & ONE OF THE MANUAL MODES IS ENABLED.
OR
NOT FIRING & BC IS IN STANDBY & “MANUAL IN RUN & STANDBY” IS ENABLED.
MIDDLE: NOT ABOVE AND BC HAS A COMMANDED RATE (E.G. IN STANDBY, PURGE, IDNITION, ETC.)
BOTTOM: FIRING & BC HAS NO COMMANDED RATE & AUTO MODE SELECTED (NORMAL MODULATION)
OFF (NO DEMAND) = 0
OFF (NO DEMAND) = 0%
DHW
demand
priority
timer
CH PUMP DEMAND
DHW PUMP DEMAND
SLAVE COMMAND EXISTS
CH FROST PROTECT BURNER DEMAND
LL SLAVE ENABLE
DHW FROST PROTECT BURNER DEMAND
DHW FROST PROTECTION ENABLE
RELOAD
CH
DHW
LL
FP
OFF
CH
DHW
LL
FP
OFF
0 = BC HAS COMMANDED FAN TO BE OFF & NOT BELOW; OR BC DISABLED/FAULT.
= MANUAL RATE WHEN FIRING IS LESS THAN MINIMUM MODULATION,
OR ABNORMAL BC REQUEST (MANUAL MODES IGNORED).
= MANUAL RATE WHEN FIRING IS GREATER THAN MAX MODULATION.
= ABNORMAL BC REQUEST OR MANUAL IN STANDBY IS LESS THAN ABS. MIN.
= ABNORMAL BC REQUEST OR MANUAL IN STANDBY IS LESS THAN ABS. MIN.
TACH
PUMP
CONTROL
BURNER
CONTROL
MODULATION
OUTPUT
MIN. MOD. RATE
FORCED RATE...
DHW PRIORITY OVERRIDE TIME
CH FROST PROTECTION ENABLE
MANUAL RATE ENABLE
- AUTO
- MANUAL IN RUN
- MANUAL IN RUN AND STANDBY
MANUAL
RATE
SELECT
IF “DHW pump demand” is true
Set DHW_storage_timer to DHW storage time
ELSE
Decrement DHW_storage_timer (count down to zero, then stop)
IF “DHW pump demand” is false
Set DHW_priority_timer to DHW priority override time
ELSE
Decrement DHW_priority_timer (count down to zero, then stop)
Summary of Contents for CFC-1000
Page 35: ...Section 2 Installation Part No 750 263 2 21 Figure 2 23 Gas Piping ...
Page 47: ...Section 2 Installation Part No 750 263 2 33 Figure 2 41 Electrical Connection Diagram ...
Page 49: ...Section 2 Installation Part No 750 263 2 35 Figure 2 43 CFC Wiring Diagram dual fuel units ...
Page 50: ...Section 2 Installation 2 36 Part No 750 263 ...
Page 70: ...Section 3 Stack and Intake Vent Sizing and Installation 3 20 Part No 750 263 ...
Page 102: ...Section 4 CFC Commissioning 4 32 Part No 750 263 ...
Page 108: ...Section 5 Service and Maintenance 5 6 Part No 750 263 ...
Page 113: ...Section 6 Parts Part No 750 263 6 5 Figure 6 3 Casing Table 6 5 Casing parts ...
Page 117: ...Section 6 Parts Part No 750 263 6 9 Figure 6 7 Electrical assemblies single fuel ...
Page 123: ...APPENDIX A CB FALCON CONTROLLER ...
Page 124: ......
Page 244: ...CB FALCON 750 265 120 ...
Page 245: ...APPENDIX B CB FALCON PLUG IN MODULE ...
Page 246: ......
Page 250: ......
Page 251: ...APPENDIX C GAS VALVE ...
Page 252: ......
Page 269: ...APPENDIX D CB FALCON MODBUS COMMUNICATION ...
Page 270: ......