CB FALCON MODBUS COMMUNICATION
21
Table 4. CB Falcon Modbus register map
01E5
0485
Delta-T retry limit
R/W
U16
Maximum number of recycles due to Delta-T or inversion
limit.
01E6
0486
Delta-T rate limit enable
R/W
U16
0=Do not limit modulation rate,
1=Limit modulation rate when approaching Delta-T
threshold
01E7
0487
Delta-T inverse limit time
R/W
U16
Minimum toleration time for temperature inversion (0-
64800 seconds)
01E8
0488
Delta-T inverse limit
response
R/W
U16
0=Lockout,
1=Recycle&delay,
2=Recycle&delay with retry limit
01E9
0489
Delta-T exchanger/outlet
enable
R/W
U16
Delta-T limit for exchanger to outlet flow:
0=Disable Delta-T limit,
1=Enable Delta-T limit,
2=Enable Inversion detection,
3=Enable Delta-T limit and Inversion detection
01EA
0490
Delta-T exchanger/outlet
degrees
R/W
U16
Temperature delta between exchanger & outlet sensors
when Delta-T limit occurs:
0°-130° (0.1°C precision)
a
01EB
0491
Exchanger T-rise enable
R/W
U16
0=Disable exchanger T-rise limit,
1=Enable exchanger T-rise limit
01EC
0492
T-rise response
R/W
U16
0=Lockout,
1=Recycle&delay,
2=Recycle&delay with retry limit
01ED
0493
T-rise retry limit
R/W
U16
Maximum number of recycles due to T-rise limit.
01EE
0494
Delta-T inlet/exchanger
enable
R/W
U16
Delta-T limit for inlet to exchanger flow:
0=Disable Delta-T limit,
1=Enable Delta-T limit,
2=Enable Inversion detection,
3=Enable Delta-T limit and Inversion detection
01EF
0495
Delta-T inlet/exchanger
degrees
R/W
U16
Temperature delta between inlet & exchanger sensors
when Delta-T limit occurs:
0°-130° (0.1°C precision)
a
ANTICONDENSATION
CONFIGURATION
01F0
0496
CH anticondensation enable R/W
U16
0=Disable CH anticondensation,
1=Enable CH anticondensation
01F1
0497
CH anticondensation
setpoint
R/W
U16
-40°-130° (0.1°C precision)
a
01F2
0498
CH anticondensation pump
force off
R/W
U16
0=Normal (no change to CH pump)
1=CH pump forced off
01F3
0499
DHW anticondensation
enable
R/W
U16
0=Disable DHW anticondensation,
1=Enable DHW anticondensation
01F4
0500
DHW anticondensation
setpoint
R/W
U16
-40°-130° (0.1°C precision)
a
01F5
0501
DHW anticondensation
pump force off
R/W
U16
0=Normal (no change to DHW pump)
1=DHW pump forced off
01F6
0502
Anticondensation priority
R/W
U16
Is anticondensation more important than (0=No, 1=Yes)?
Bit map:
15-5=Reserved (always 0)
4=Outlet high limit
3=Forced rate
2=Slow start
1=Delta-T limit
0=Stack limit
01F7
0503
Frost protection
anticondensation enable
R/W
U16
0=Disable frost protection anticondensation,
1=Enable frost protection anticondensation
Summary of Contents for CFC-1000
Page 35: ...Section 2 Installation Part No 750 263 2 21 Figure 2 23 Gas Piping ...
Page 47: ...Section 2 Installation Part No 750 263 2 33 Figure 2 41 Electrical Connection Diagram ...
Page 49: ...Section 2 Installation Part No 750 263 2 35 Figure 2 43 CFC Wiring Diagram dual fuel units ...
Page 50: ...Section 2 Installation 2 36 Part No 750 263 ...
Page 70: ...Section 3 Stack and Intake Vent Sizing and Installation 3 20 Part No 750 263 ...
Page 102: ...Section 4 CFC Commissioning 4 32 Part No 750 263 ...
Page 108: ...Section 5 Service and Maintenance 5 6 Part No 750 263 ...
Page 113: ...Section 6 Parts Part No 750 263 6 5 Figure 6 3 Casing Table 6 5 Casing parts ...
Page 117: ...Section 6 Parts Part No 750 263 6 9 Figure 6 7 Electrical assemblies single fuel ...
Page 123: ...APPENDIX A CB FALCON CONTROLLER ...
Page 124: ......
Page 244: ...CB FALCON 750 265 120 ...
Page 245: ...APPENDIX B CB FALCON PLUG IN MODULE ...
Page 246: ......
Page 250: ......
Page 251: ...APPENDIX C GAS VALVE ...
Page 252: ......
Page 269: ...APPENDIX D CB FALCON MODBUS COMMUNICATION ...
Page 270: ......