Section 4 — CFC Commissioning
Part No. 750-263
4-29
The PID (Proportional-Integral-Derivative) load control operates to
generate the demand source’s modulation rate. Under Central Heat
configuration, the PID gain values can be adjusted to match the
desired modulation response. The default gain value settings of
P=25, I=25 & D=0 have proven to work well with typical
applications.
Remote Enable and Remote 4-20mA Input
Remote enable and Remote 4-20mA input allow the boiler to be
sequenced and/or controlled from a separate boiler room controller
or building management system. The 3-position Demand switch at
the front of the control panel determines whether the boiler is off, in
local, or under remote control. When in the “LOC” (local) position,
the boiler operates on its own set point and ignores any remote
signal connections. When in the “REM” (remote) position, the
boiler can be enabled and modulated by remote discrete and analog
(4-20mA) inputs, respectively. When in the “OFF” position, the
boiler will not operate.
Refer to Figure 2-10 in this manual or to your specific boiler wiring
diagram for remote enable and remote 4-20mA input connections.
For simple remote on-off sequencing, only terminals 24 and 25
(Falcon J8-1 & J8-3) need to be connected to dry enable contacts
at the remote controller. When terminal 25 (demand input) is
energized, the demand is enabled. The boiler operates on its local
set point and PID modulating control settings.
For
remote modulation
(firing rate) control, both the remote enable
and remote 4-20mA input connections must be made. The default
setting for the 4-20mA remote input is “Local”. This setting should
be verified under the Falcon control’s Central Heat configuration
group, “Central Heat>Modulation>Modulation Rate Source”. For
remote modulation this parameter should be set to “S2 (J8-6) 4-20
mA with sensor on-off.
To avoid nuisance operating limit shut downs of the boiler, the
Falcon’s normal operating set point should be adjusted to a value
that is greater than the system header set point.
With demand present and completion of a successful trial for
ignition sequence, the boiler will modulate according to the 4-20mA
input signal provided: 4mA = minimum modulation rate (low fire);
20mA = maximum modulation rate (high fire). The boiler will
continue to modulate until the demand is removed, the operating
limit is reached, LCI is opened (e.g. low water condition), or a
Falcon lockout alarm occurs (e.g. ILK opens on a High Limit trip).
To configure the boiler for
remote set point
control, navigate to the
Falcon control’s Central Heat configuration group. Change the
setting of “Central Heat Configuration>Set Point>Set Point Source”
to “S2 (J8-6) 4-20mA”. Next, the span of the 4-20mA needs to be
established. The active set point determines the value for 20mA;
“minimum water temperature” determines the value for 4mA.
Summary of Contents for CFC-1000
Page 35: ...Section 2 Installation Part No 750 263 2 21 Figure 2 23 Gas Piping ...
Page 47: ...Section 2 Installation Part No 750 263 2 33 Figure 2 41 Electrical Connection Diagram ...
Page 49: ...Section 2 Installation Part No 750 263 2 35 Figure 2 43 CFC Wiring Diagram dual fuel units ...
Page 50: ...Section 2 Installation 2 36 Part No 750 263 ...
Page 70: ...Section 3 Stack and Intake Vent Sizing and Installation 3 20 Part No 750 263 ...
Page 102: ...Section 4 CFC Commissioning 4 32 Part No 750 263 ...
Page 108: ...Section 5 Service and Maintenance 5 6 Part No 750 263 ...
Page 113: ...Section 6 Parts Part No 750 263 6 5 Figure 6 3 Casing Table 6 5 Casing parts ...
Page 117: ...Section 6 Parts Part No 750 263 6 9 Figure 6 7 Electrical assemblies single fuel ...
Page 123: ...APPENDIX A CB FALCON CONTROLLER ...
Page 124: ......
Page 244: ...CB FALCON 750 265 120 ...
Page 245: ...APPENDIX B CB FALCON PLUG IN MODULE ...
Page 246: ......
Page 250: ......
Page 251: ...APPENDIX C GAS VALVE ...
Page 252: ......
Page 269: ...APPENDIX D CB FALCON MODBUS COMMUNICATION ...
Page 270: ......