Whenever the burner turns off, the turn-on threshold is lowered
by doubling the on hysteresis, and then increasing it by 2
degrees F per step until it reaches its original value.
The time of each step is provided by the hysteresis step time
parameter. The number of steps required to reach the original
on hysteresis is the on hysteresis value divided by
2 degrees F.
Fig. 12. Hydronic Setpoint and hysteresis.
Setpoint and Hysteresis (Steam
Control)
The Steam and LL master each have similar setpoint and
hysteresis functions. The parameters for each are separate
and independent.
Whenever the burner turns on, the turn-off threshold is raised
by 10psi (1.0 for 0-15 psi), and then it is decreased in steps.
The time of each step is provided by the hysteresis step time
parameter. If the time (T) is not-zero, then the following
schedule is followed until the off threshold reaches its original
value:
Whenever the burner turns off, the turn-on threshold is lowered
by doubling the on hysteresis, and then increasing it by 2 psi
(.2 psi for 0-15 psi) per step until it reaches its original value.
The time of each step is provided by the hysteresis step time
parameter. The number of steps required to reach the original
on hysteresis is the on hysteresis value divided by 2 psi per
step for (0–150 PSI .2 psi per step for; 0–15 PSI).
Step
Time since turn-on Hydronic Turn-on threshold
1
0<=timer <1T
Setpoint - 2 * On hysteresis
2
1T<=time <2T
Setpoint - 2 * On hyst
1*2°F
3
2T<=time <3T
Setpoint - 2 * On hyst
2* 2°F
4
nT<=time <(n+1)T
Setpoint -2 * On hyst n
* 2°F
5
(on hysteresis/
2F*T<=time
Setpoint
SE OFF HYSTERESIS
SETPOINT
SETPOINT - ON HYSTERESIS
BURNER
+18°F
+8°F
+6°F
+4°F
+2°F
1 MINUTE
SETPOINT - 2 * ON HYSTERESIS
1 MINUTE
OFF
ON
ANTI-SHORT-CYCLE DELAY
SETPOINT AND HYSTERESIS
HST = HISTERESIS STEP TIME
(0 = DISABLE)
2°F
ANTI SHORT CYCLE DELAY TIME
(DOES NOT APPLY FOR DHW)
TOD SETPOINT
SETPOINT
ON HYST.
OFF HYST.
CH PARAMETERS
SYSTEM PARAMETER
TOD SETPOINT
SETPOINT
ON HYST.
OFF HYST.
DHW PARAMETERS
TOD SETPOINT
HYSTERESIS STEP TIME
HYSTERESIS STEP TIME
HYSTERESIS STEP TIME
SETPOINT
ON HYST.
OFF HYST.
LL MASTER PARAMETERS
Steam Turn-off Threshold
Step
150psi Sensor
15psi Sensor
1
10
1.0
2
8
0.8
3
6
0.6
4
4
0.4
5
2
0.2
6
Setpoint
Setpoint
Steam Turn-on Threshold
Step
150psi Sensor
15psi Sensor
1
0<=timer<1T
Setpoint - 2* On
hysteresis
2
1T<=time<2T
Setpoint - 2 * On
hyst .2psi
3
2T<=time<3T
Setpoint - 2 * On
hyst .2psi
4
nT<=time<(n+1)T
Setpoint - 2 * On
hyst .2psi
5
(on hysteresis/
2psi<=time)
Setpoint
Summary of Contents for CFC-1000
Page 35: ...Section 2 Installation Part No 750 263 2 21 Figure 2 23 Gas Piping ...
Page 47: ...Section 2 Installation Part No 750 263 2 33 Figure 2 41 Electrical Connection Diagram ...
Page 49: ...Section 2 Installation Part No 750 263 2 35 Figure 2 43 CFC Wiring Diagram dual fuel units ...
Page 50: ...Section 2 Installation 2 36 Part No 750 263 ...
Page 70: ...Section 3 Stack and Intake Vent Sizing and Installation 3 20 Part No 750 263 ...
Page 102: ...Section 4 CFC Commissioning 4 32 Part No 750 263 ...
Page 108: ...Section 5 Service and Maintenance 5 6 Part No 750 263 ...
Page 113: ...Section 6 Parts Part No 750 263 6 5 Figure 6 3 Casing Table 6 5 Casing parts ...
Page 117: ...Section 6 Parts Part No 750 263 6 9 Figure 6 7 Electrical assemblies single fuel ...
Page 123: ...APPENDIX A CB FALCON CONTROLLER ...
Page 124: ......
Page 244: ...CB FALCON 750 265 120 ...
Page 245: ...APPENDIX B CB FALCON PLUG IN MODULE ...
Page 246: ......
Page 250: ......
Page 251: ...APPENDIX C GAS VALVE ...
Page 252: ......
Page 269: ...APPENDIX D CB FALCON MODBUS COMMUNICATION ...
Page 270: ......