CB FALCON MODBUS COMMUNICATION
17
Table 4. CB Falcon Modbus register map
011B
0283
Boiler pump overrun time
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
011C
0284
Auxiliary 1 pump output
R/W
U16
0=None, 1=Pump A, 2=Pump B, 3=Pump C
011D
0285
Auxiliary 1 pump control
R/W
U16
0=Auto, 1=On
011E
0286
RESERVED
011F
0287
System pump output
R/W
U16
0=None, 1=Pump A, 2=Pump B, 3=Pump C
0120
0288
System pump control
R/W
U16
0=Auto, 1=On
0121
0289
System pump overrun time
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
0122
0290
Pump exercise interval
R/W
U16
Days
0123
0291
Pump exercise time
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
0124
0292
CH pump start delay
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
0125
0293
Boiler pump start delay
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
0126
0294
System pump start delay
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
0127
0295
Auxiliary 1 pump start delay R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
0128
0296
CH pump options 1
R/W
U16
Bit map:
15=Normal pump demand when auxiliary pump Z is set,
14=Normal pump demand when auxiliary pump Y is set,
13=Normal pump demand when auxiliary pump X is set,
12-7=Reserved (always 0),
6=Normal pump demand when DHW service is active,
5=Normal pump demand when CH service is active,
4=Reserved,
3=Normal pump demand when DHW demand,
2=Normal pump demand when CH demand,
1=Normal pump demand when local burner demand,
0=Local demand inhibited for faults
0129
0297
CH pump options 2
R/W
U16
Bit map:
15=Pump used for Lead Lag,
14=Pump used for local demand,
13-9=Reserved (always 0),
8=Force pump off when DHW high limit,
7=Force pump off when DHW anti-condensation,
6=Force pump off when CH anti-condensation,
5=Force pump off when DHW priority is active,
4=Force pump on when DHW frost protection,
3=Force pump on when CH frost protection,
2=Force pump on when Lead Lag slave demand,
1=Force pump on when local burner demand,
0=Force pump on when Outlet high limit
012A
0298
DHW pump options 1
R/W
U16
Bit map:
15=Normal pump demand when auxiliary pump Z is set,
14=Normal pump demand when auxiliary pump Y is set,
13=Normal pump demand when auxiliary pump X is set,
12-7=Reserved (always 0),
6=Normal pump demand when DHW service is active,
5=Normal pump demand when CH service is active,
4=Reserved,
3=Normal pump demand when DHW demand,
2=Normal pump demand when CH demand,
1=Normal pump demand when local burner demand,
0=Local demand inhibited for faults
Summary of Contents for CFC-1000
Page 35: ...Section 2 Installation Part No 750 263 2 21 Figure 2 23 Gas Piping ...
Page 47: ...Section 2 Installation Part No 750 263 2 33 Figure 2 41 Electrical Connection Diagram ...
Page 49: ...Section 2 Installation Part No 750 263 2 35 Figure 2 43 CFC Wiring Diagram dual fuel units ...
Page 50: ...Section 2 Installation 2 36 Part No 750 263 ...
Page 70: ...Section 3 Stack and Intake Vent Sizing and Installation 3 20 Part No 750 263 ...
Page 102: ...Section 4 CFC Commissioning 4 32 Part No 750 263 ...
Page 108: ...Section 5 Service and Maintenance 5 6 Part No 750 263 ...
Page 113: ...Section 6 Parts Part No 750 263 6 5 Figure 6 3 Casing Table 6 5 Casing parts ...
Page 117: ...Section 6 Parts Part No 750 263 6 9 Figure 6 7 Electrical assemblies single fuel ...
Page 123: ...APPENDIX A CB FALCON CONTROLLER ...
Page 124: ......
Page 244: ...CB FALCON 750 265 120 ...
Page 245: ...APPENDIX B CB FALCON PLUG IN MODULE ...
Page 246: ......
Page 250: ......
Page 251: ...APPENDIX C GAS VALVE ...
Page 252: ......
Page 269: ...APPENDIX D CB FALCON MODBUS COMMUNICATION ...
Page 270: ......