CB FALCON MODBUS COMMUNICATION
16
Table 4. CB Falcon Modbus register map
00F6
0246
Interrupted air switch (IAS)
enable
R/W
U16
SAFETY
parameter
f
:
0=Disable,
1=Enable during purge,
2=Enable during purge & ignition,
3=Enable during all states
00F7
0247
IAS start check enable
R/W
U16
SAFETY
parameter
f
:
0=Disable, 1=Enable
00F8
0248
LCI enable
R/W
U16
SAFETY
parameter
f
::
0=Disable, 1=Enable
00F9
0249
PII enable
R/W
U16
SAFETY
parameter
f
:
0=Disable, 1=Enable
00FA
0250
Flame threshold
R/W
U16
SAFETY
parameter
f
:
Minimum microamps needed to declare flame presence
(0.1A precision). Default value is 0.8 A (8).
00FB-00FC
0251-0252
RESERVED
00FD
0253
ILK bounce detection
R/W
U16
SAFETY
parameter
f
:
0=Do not check for ILK bounce,
1=Check for ILK bounce
00FE
0254
Forced recycle interval time R/W
U16
SAFETY
parameter
f
:
0=No forced recycle,
1-64800 minutes (1080 hours), 0xFFFF=Not configured
00FF
0255
RESERVED
FAN CONFIGURATION
0100
0256
Absolute maximum fan
speed
R/W
U16
RPM
0101
0257
Absolute minimum fan
speed
R/W
U16
RPM
0102
0258
Fan PWM frequency
R/W
U16
0=Unknown,
1=1000 Hz,
2=2000 Hz,
3=3000 Hz,
4=4000 Hz,
0xFFFF=Not configured
0103
0259
Fan pulses per revolution
R/W
U16
1-10
0104
0260
Fan speed-up ramp
R/W
U16
0-7000 RPM/sec
0105
0261
Fan slow-down ramp
R/W
U16
0-7000 RPM/sec
0106
0262
Fan gain up
R/W
U16
0-65535
0107
0263
Fan gain down
R/W
U16
0-65535
0108
0264
Fan minimum duty cycle
R/W
U16
1-100%
b
0109-010F
0265-0271
RESERVED
PUMP CONFIGURATION
0110
0272
CH pump output
R/W
U16
0=None, 1=Pump A, 2=Pump B, 3=Pump C
0111
0273
CH pump control
R/W
U16
0=Auto, 1=On
0112
0274
CH pump overrun time
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
0113
0275
CH FP pump overrun time
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
0114
0276
DHW pump output
R/W
U16
0=None, 1=Pump A, 2=Pump B, 3=Pump C
0115
0277
DHW pump control
R/W
U16
0=Auto, 1=On
0116
0278
DHW pump overrun time
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
0117
0279
DHW FP pump overrun time R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
0118
0280
DHW pump start delay
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
0119
0281
Boiler pump output
R/W
U16
0=None, 1=Pump A, 2=Pump B, 3=Pump C
011A
0282
Boiler pump control
R/W
U16
0=Auto, 1=On
Summary of Contents for CFC-1000
Page 35: ...Section 2 Installation Part No 750 263 2 21 Figure 2 23 Gas Piping ...
Page 47: ...Section 2 Installation Part No 750 263 2 33 Figure 2 41 Electrical Connection Diagram ...
Page 49: ...Section 2 Installation Part No 750 263 2 35 Figure 2 43 CFC Wiring Diagram dual fuel units ...
Page 50: ...Section 2 Installation 2 36 Part No 750 263 ...
Page 70: ...Section 3 Stack and Intake Vent Sizing and Installation 3 20 Part No 750 263 ...
Page 102: ...Section 4 CFC Commissioning 4 32 Part No 750 263 ...
Page 108: ...Section 5 Service and Maintenance 5 6 Part No 750 263 ...
Page 113: ...Section 6 Parts Part No 750 263 6 5 Figure 6 3 Casing Table 6 5 Casing parts ...
Page 117: ...Section 6 Parts Part No 750 263 6 9 Figure 6 7 Electrical assemblies single fuel ...
Page 123: ...APPENDIX A CB FALCON CONTROLLER ...
Page 124: ......
Page 244: ...CB FALCON 750 265 120 ...
Page 245: ...APPENDIX B CB FALCON PLUG IN MODULE ...
Page 246: ......
Page 250: ......
Page 251: ...APPENDIX C GAS VALVE ...
Page 252: ......
Page 269: ...APPENDIX D CB FALCON MODBUS COMMUNICATION ...
Page 270: ......