Section 4 — CFC Commissioning
Part No. 750-263
4-7
• Burner Control Interlocks
• Burner Control Timings & Rates
• Burner Control Ignition
• Burner Control Flame Failure
• System Configuration
• Fan Configuration
• Lead Lag Configuration
Table 4-1 CFC default parameter settings
Parameter Group
Parameter Name
Access*
Min.
Range
Default Setting
Max.
Range
Parameter
Units
Installation Setting
Modbus
Register
(dec)
System ID & Access
Boiler Name
Service
Boiler 1
0183
System ID & Access
Installation data
Service
SERIAL NUMBER
0184
System ID & Access
OEM Identification
Read Only
CB FALCON 833-
03639
0185
System ID & Access
Installer password
Service
9220
0190
System ID & Access
Modbus address
Service
0
1
250
????
System ID & Access
Factory data
Read Only
????
Central Heat Configuration
CH enable
Service
Enabled
0208
Central Heat Configuration
CH demand source
Service
Stat terminal
0209
Central Heat Configuration
CH modulation sensor
Service
Modulation from Outlet
sensor (S3S4)
0210
Central Heat Configuration
CH setpoint
User
32
150
194
°F
0211
Central Heat Configuration
CH TOD setpoint
User
32
120
194
°F
0212
Central Heat Configuration
CH on hysteresis
Service
2
5
60
°F
0213
Central Heat Configuration
CH off hysteresis
Service
2
15
60
°F
0214
Central Heat Configuration
CH outdoor reset enable
Service
Disabled
0215
Central Heat Configuration
CH P gain
Service
0
25
400
0216
Central Heat Configuration
CH I gain
Service
0
25
400
0217
Central Heat Configuration
CH D gain
Service
0
0
400
0218
Central Heat Configuration
CH hysteresis step time
Service
0
60
900
seconds
0219
Central Heat Configuration
CH setpoint source
Service
Local SP
0578
Central Heat Configuration
CH modulation source
Service
Local Modulation (PID)
0580
Central Heat Configuration
CH has priority over LL
Service
No
0582
Central Heat Configuration
CH 4mA water temperature
Service
60
0583
Central Heat Configuration
CH 20mA water temperature
Service
180
0584
Outdoor Reset Configuration
CH ODR max. outdoor
temperature
Service
-40
80
140
°F
0512
Outdoor Reset Configuration
CH ODR min. outdoor
temperature
Service
-40
0
140
°F
0513
Outdoor Reset Configuration
CH ODR low water
temperature
Service
32
80
180
°F
0514
Outdoor Reset Configuration
CH ODR maximum off point
Service
32
194
210
°F
0516
Outdoor Reset Configuration
Minimum boiler water
temperature
Service
32
80
180
°F
0526
Domestic HW Configuration
DHW enable
User
Disabled
0448
Domestic HW Configuration
DHW demand switch
Service
DHW switch (S6) or
sensor only
0449
Domestic HW Configuration
DHW priority has priority over
CH
Service
Yes
0450
Domestic HW Configuration
DHW priority has priority over
LL
Service
Yes
0451
Domestic HW Configuration
DHW priority override time
Service
0
1800
14400
seconds
0452
Summary of Contents for CFC-1000
Page 35: ...Section 2 Installation Part No 750 263 2 21 Figure 2 23 Gas Piping ...
Page 47: ...Section 2 Installation Part No 750 263 2 33 Figure 2 41 Electrical Connection Diagram ...
Page 49: ...Section 2 Installation Part No 750 263 2 35 Figure 2 43 CFC Wiring Diagram dual fuel units ...
Page 50: ...Section 2 Installation 2 36 Part No 750 263 ...
Page 70: ...Section 3 Stack and Intake Vent Sizing and Installation 3 20 Part No 750 263 ...
Page 102: ...Section 4 CFC Commissioning 4 32 Part No 750 263 ...
Page 108: ...Section 5 Service and Maintenance 5 6 Part No 750 263 ...
Page 113: ...Section 6 Parts Part No 750 263 6 5 Figure 6 3 Casing Table 6 5 Casing parts ...
Page 117: ...Section 6 Parts Part No 750 263 6 9 Figure 6 7 Electrical assemblies single fuel ...
Page 123: ...APPENDIX A CB FALCON CONTROLLER ...
Page 124: ......
Page 244: ...CB FALCON 750 265 120 ...
Page 245: ...APPENDIX B CB FALCON PLUG IN MODULE ...
Page 246: ......
Page 250: ......
Page 251: ...APPENDIX C GAS VALVE ...
Page 252: ......
Page 269: ...APPENDIX D CB FALCON MODBUS COMMUNICATION ...
Page 270: ......