CB FALCON
39
750-265
Fig. 16. DHW storage.
Table 15. DHW Storage Demand Parameters.
Parameter
Comment
DHW storage enable
Enable, Disable
This parameter enables or disables the DHW storage feature. If it is disabled then the other
parameters below are ignored.
DHW storage time
mm:ss
The time DHW storage temperature is maintained.
DHW storage setpoint
degrees or None
The temperature setpoint that the boiler maintains during the DHW storage time.
DHW storage on hysteresis
degrees or None
This provides the on hysteresis as an offset that is applied to the DHW storage setpoint, used
during DHW storage demand.
DHW storage off hysteresis
degrees or None
This provides the off hysteresis as an offset that is applied to the DHW storage setpoint, used
during DHW storage demand.
DHW
DHW
TOD
SET
TIMER
LOAD
CLR
FORCE TAP
TAP
PREHEAT
PREHEAT IS ACTIVE
TAP DETECT MINIMUM ON TIME
TAP DEMAND ENDS WHEN:
PRIORITY
IS
DHW
DHW
PLATE
DEMAND
AND
AND
AND
AND
AND
OR
OR
IF DHW PLATE
DEMAND LOSES
CONTROL DUE TO
PRIORITY, RESET AND
RESTART THE ITEMS.
OTHERS CONTINUE TO
OPERATE.
DHW FORCE TAP PREHEAT
WHENEVER PREHEAT IS FALSE:
IF TAP IS TRUE, INHIBIT THIS PREHEAT BLOCK, RESET THE
ITEMS, AND RESET THE PREHEAT DELAY-AFTER-TAP TIMER.
IF PREHEAT IS FALSE, IT BECOMES TRUE WHEN:
WHEN THESE HAVE OCCURRED, THEN A 1 MINUTE TIMER STARTS.
WHEN THIS TIME ELAPSES, THEN PREHEAT ENDS. THE FORCE OUTPUT IS PULSE
TO FORCE TAP DETECTION TO START (AND PREHEAT IS INHIBITED). THIS ALSO
OCCURS IMMEDIATELY IF THE 1 MINUTE TIMEOUT IS PENDING BUT PREHEAT
ENDS DUE TO ABOVE.
WHEN PREHEAT TURNS ON, ITS MINIMUM ON TIME IS STARTED
IF PREHEAT IS TRUE, IT BECOMES FALSE WHEN:
IF TAP IS FALSE, ALLOW THE TIMER TO RUN.
•TIME IS EXPIRED, AND
•SET IS FALSE, AND
•CLR IS TRUE
•TAP DURING PREHEAT IS RECOGNIZED AS:
• TAP HAS BEEN TRUE WHILE PREHEAT WAS TRUE
• EITHER • INLET TEMPERATURE DECREASES BELOW THE LEVEL
IT HAD WHEN PREHEAT STARTED
• DHW >= INLET
•TAP DURING PREHEAT IS RECOGNIZED (SEE BELOW)
•BOTH: • DHW <= PREHEAT (SOFF HYSTERESIS)
• PREHEAT MINIMUM ON TIME HAS EXPIRED
•TAP IS FALSE
•THE PREHEAT DELAY-AFTER-TAP TIME HAS ELAPSED
• DHW <= PREHEAT (SETPOINT-ON HYSTERESIS)
•THE ABOVE HAVE PERSISTED FOR THE ON RECOGNITION TIME
WHENEVER SET CHANGES FROM OFF TO ON,
TAP OUTPUT IS TRUE FOR AT LEAST THE
TAP
PREHEAT
TRUE IF DHW <= SETPOINT-
TRUE IF INLETTEMP-DHW =>-
INLETTEMP
INLET
OUTLETTEMP
OUTLET(S3S4)
INLETTEMP
INLET (S1)
TRUE IF OUTLETTEMP-
INLETTEMP<
=
AND THIS PERSISTS FOR LONGER THAN:
DHW
TAP DETECT DEGREES PER SECOND
TRUE WHILE DHW IS
DROPPING FASTER THAN
SETPOINT
SELECT
TOD SETPOINT
TAP DETECT ON HYSTERESIS
TIMER
PLATE PREHEAT ON HYSTERESIS
PLATE PREHEAT ON RECOGNITION TIME
PLATE PREHEAT DELAY AFTER TAP
PLATE PREHEAT MINIMUM ON TIME
PLATE PREHEAT OFF HYSTERESIS
PLATE PREHEAT SETPOINT
TAP DETECT RECOGNITION TIME
TAP STOP INLET -DHW DEGREES
TAP STOP OUTLET -INLET DEGREES
TIMER
FLAG
TIMER
TIMER
TIMER
IF FORCE IS ON, TREAT AS
IF SET HAD JUST CHANGED
FROM OFF TO ON.
IF BOTH SET AND
CLR ARE TRUE,
IGNORE CLR
DHW PLATE DEMAND
DHW MODULATION SENSOR
Summary of Contents for CFC-1000
Page 35: ...Section 2 Installation Part No 750 263 2 21 Figure 2 23 Gas Piping ...
Page 47: ...Section 2 Installation Part No 750 263 2 33 Figure 2 41 Electrical Connection Diagram ...
Page 49: ...Section 2 Installation Part No 750 263 2 35 Figure 2 43 CFC Wiring Diagram dual fuel units ...
Page 50: ...Section 2 Installation 2 36 Part No 750 263 ...
Page 70: ...Section 3 Stack and Intake Vent Sizing and Installation 3 20 Part No 750 263 ...
Page 102: ...Section 4 CFC Commissioning 4 32 Part No 750 263 ...
Page 108: ...Section 5 Service and Maintenance 5 6 Part No 750 263 ...
Page 113: ...Section 6 Parts Part No 750 263 6 5 Figure 6 3 Casing Table 6 5 Casing parts ...
Page 117: ...Section 6 Parts Part No 750 263 6 9 Figure 6 7 Electrical assemblies single fuel ...
Page 123: ...APPENDIX A CB FALCON CONTROLLER ...
Page 124: ......
Page 244: ...CB FALCON 750 265 120 ...
Page 245: ...APPENDIX B CB FALCON PLUG IN MODULE ...
Page 246: ......
Page 250: ......
Page 251: ...APPENDIX C GAS VALVE ...
Page 252: ......
Page 269: ...APPENDIX D CB FALCON MODBUS COMMUNICATION ...
Page 270: ......