CB FALCON
103
750-265
Annunciator 4 location
Read Only
A:No annunciation
for this terminal
Annunciator4 short name
Read Only
A4
3 chars
Annunciator 4 long name
Read Only
Annunciator4
20 chars
Annunciator 5 location
Read Only
E:No annunciation
for this terminal
Annunciator5 short name
Read Only
A5
3 chars
Annunciator 5 long name
Read Only
Annunciator5
20 chars
Annunciator 6 location
Read Only
E:No annunciation
for this terminal
Annunciator6 short name
Read Only
A6
3 chars
Annunciator 6 long name
Read Only
Annunciator6
20 chars
Annunciator 7 location
Read Only
E:No annunciation
for this terminal
Annunciator7 short name
Read Only
A7
3 chars
Annunciator 7 long name
Read Only
Annunciator7
20 chars
Annunciator 8 location
Read Only
E:No annunciation
for this terminal
Annunciator8 short name
Read Only
A8
3 chars
Annunciator 8 long name
Read Only
Annunciator8
20 chars
PII short name
Read Only
PII
3 chars
PII long name
Read Only
Pre-Ignition ILK
20 chars
LCI short name
Read Only
LCI
3 chars
LCI long name
Read Only
Load Control Input
20 chars
ILK short name
Read Only
ILK
3 chars
ILK long name
Read Only
Interlock
20 chars
DHW enable
Read Only
Disabled
DHW demand source
Read Only
A:DHW sensor
only
DHW has priority over CH
Read Only
No/False/Off
DHW has priority over LL
Read Only
No/False/Off
DHW priority time
Read Only
30m 0s
mmm:ss
DHW setpoint
Read Only
32°F 0°C
140°F 60°C
240°F 116°C
DHW tod setpoint
Read Only
32°F 0°C
120°F 49°C
240°F 116°C
DHW on hysteresis
Read Only
2°F 1°C
5°F 3°C
100°F 56°C
DHW off hysteresis
Read Only
2°F 1°C
5°F 3°C
100°F 56°C
DHW P gain
Read Only
0
50
400
DHW I gain
Read Only
0
50
400
DHW D gain
Read Only
0
50
400
DHW hysteresis step time
Read Only
0m 0s
mmm:ss
Outlet high limit setpoint
Read Only
32°F 0°C
220°F 104°C
240°F 116°C
Outlet high limit response
Read Only
[ A B #c #d ]
A:Lockout
Stack limit enable
Read Only
Disabled
Stack limit setpoint
Read Only
32°F 0°C
200°F 93°C
500°F 260°C
Stack limit response
Read Only
[ A #b C #d ]
A:Lockout
Table 48. Example of a Completed Device Parameter Worksheet. (Continued)
Parameter Name
Customer
Choice - Hidden,
Read Only or
Password
protected
Minimum Range
Default Setting
Maximum Range Parameter Units
Summary of Contents for CFC-1000
Page 35: ...Section 2 Installation Part No 750 263 2 21 Figure 2 23 Gas Piping ...
Page 47: ...Section 2 Installation Part No 750 263 2 33 Figure 2 41 Electrical Connection Diagram ...
Page 49: ...Section 2 Installation Part No 750 263 2 35 Figure 2 43 CFC Wiring Diagram dual fuel units ...
Page 50: ...Section 2 Installation 2 36 Part No 750 263 ...
Page 70: ...Section 3 Stack and Intake Vent Sizing and Installation 3 20 Part No 750 263 ...
Page 102: ...Section 4 CFC Commissioning 4 32 Part No 750 263 ...
Page 108: ...Section 5 Service and Maintenance 5 6 Part No 750 263 ...
Page 113: ...Section 6 Parts Part No 750 263 6 5 Figure 6 3 Casing Table 6 5 Casing parts ...
Page 117: ...Section 6 Parts Part No 750 263 6 9 Figure 6 7 Electrical assemblies single fuel ...
Page 123: ...APPENDIX A CB FALCON CONTROLLER ...
Page 124: ......
Page 244: ...CB FALCON 750 265 120 ...
Page 245: ...APPENDIX B CB FALCON PLUG IN MODULE ...
Page 246: ......
Page 250: ......
Page 251: ...APPENDIX C GAS VALVE ...
Page 252: ......
Page 269: ...APPENDIX D CB FALCON MODBUS COMMUNICATION ...
Page 270: ......