CB FALCON MODBUS COMMUNICATION
13
Table 4. CB Falcon Modbus register map
00B4
0180
Alarm silence time
R/W
U16
0-600 minutes
00B5
0181
Power up with lockout
R/W
U16
SAFETY
parameter
f
:
0=Clear lockout on power-up (reset),
1=Do not clear lockout on power-up (preserve)
00B6
01820182
Reset and restart
W
U16
Force soft reset of Falcon subsystems:
0=None,
1=Burner control,
2=Application,
3=Burner control & application,
4=Clear alert log
Successful login required before request is granted.
00B7
0183
Burner name
R/W
Variable length string (up to 20 characters)
00B8
0184
Installation data
R/W
Variable length string (up to 20 characters)
00B9
0185
OEM ID
R/W
Variable length string (up to 20 characters)
00BA
0186
OS number
R
Variable length string (up to 16 characters)
00BB
0187
Date code
R
Variable length string (up to 10 characters)
00BC
0188
Safety Processor build
R
U16
00BD
0189
Application Processor build
R
U16
00BE
0190
Installer password
W
To set new installer password (up to 20 characters).
Requires register access status (register 177) set to
Installer or higher.
00BF
0191
OEM password
W
To set new OEM password (up to 20 characters).
Requires register access status (register 177) set to
OEM or higher.
MODULATION
CONFIGURATION
00C0
0192
Modulation output
R/W
U16
SAFETY
parameter
f
:
0=Fan PWM,
1=0-10V,
2=4-20mA
00C1
0193
CH maximum modulation
rate
R/W
U16
RPM or %
c
00C2
0194
DHW maximum modulation
rate
R/W
U16
RPM or %
c
00C3
0195
Minimum modulation rate
R/W
U16
RPM or %
c
00C4
0196
Prepurge rate
R/W
U16
SAFETY
parameter
f
:
RPM or %
c
00C5
0197
Lightoff rate
R/W
U16
SAFETY
parameter
f
:
RPM or %
c
00C6
0198
Postpurge rate
R/W
U16
SAFETY
parameter
f
:
RPM or %
c
00C7
0199
CH forced rate
R/W
U16
RPM or %
c
00C8
0200
CH forced rate time
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
00C9
0201
DHW forced rate
R/W
U16
RPM or %
c
00CA
0202
DHW forced rate time
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
00CB
0203
Burner switch
R/W
U16
0=Off, 1=On. Used to enable/disable burner control.
00CC
0204
Firing rate control
R/W
U16
0=Auto,
1=Manual in Run,
2=Manual in Run & Standby
00CD
0205
Manual firing rate
R/W
U16
Firing rate used when control is set to manual (% or
RPM
c
)
00CE
0206
Analog output hysteresis
R/W
U16
0-10V/4-20mA modulation output hysteresis. Setting of
0-10.
Summary of Contents for CFC-1000
Page 35: ...Section 2 Installation Part No 750 263 2 21 Figure 2 23 Gas Piping ...
Page 47: ...Section 2 Installation Part No 750 263 2 33 Figure 2 41 Electrical Connection Diagram ...
Page 49: ...Section 2 Installation Part No 750 263 2 35 Figure 2 43 CFC Wiring Diagram dual fuel units ...
Page 50: ...Section 2 Installation 2 36 Part No 750 263 ...
Page 70: ...Section 3 Stack and Intake Vent Sizing and Installation 3 20 Part No 750 263 ...
Page 102: ...Section 4 CFC Commissioning 4 32 Part No 750 263 ...
Page 108: ...Section 5 Service and Maintenance 5 6 Part No 750 263 ...
Page 113: ...Section 6 Parts Part No 750 263 6 5 Figure 6 3 Casing Table 6 5 Casing parts ...
Page 117: ...Section 6 Parts Part No 750 263 6 9 Figure 6 7 Electrical assemblies single fuel ...
Page 123: ...APPENDIX A CB FALCON CONTROLLER ...
Page 124: ......
Page 244: ...CB FALCON 750 265 120 ...
Page 245: ...APPENDIX B CB FALCON PLUG IN MODULE ...
Page 246: ......
Page 250: ......
Page 251: ...APPENDIX C GAS VALVE ...
Page 252: ......
Page 269: ...APPENDIX D CB FALCON MODBUS COMMUNICATION ...
Page 270: ......