CB FALCON MODBUS COMMUNICATION
19
Table 4. CB Falcon Modbus register map
ANNUNCIATION
CONFIGURATION
0130
0304
Annunciation enable
R/W
U16
0=Annunciation disabled,
1=Annunciation enabled
0131
0305
Annunciator mode
R/W
U16
0=Fixed,
1=Programmable
0132-013E
0306-0318
Annunciator 1 configuration R/W
See table 6.
013F-014B
0319-0331
Annunciator 2 configuration R/W
See table 6.
014C-0158
0332-0344
Annunciator 3 configuration R/W
See table 6.
0159-0165
0345-0357
Annunciator 4 configuration R/W
See table 6.
0166-0172
0358-0370
Annunciator 5 configuration R/W
See table 6.
0173-017F
0371-0383
Annunciator 6 configuration R/W
See table 6.
0180-018C
0384-0396
Annunciator 7 configuration R/W
See table 6.
018D-0199
0397-0409
Annunciator 8 configuration R/W
See table 6.
019A-01A5
0410-0421
PII configuration
R/W
See table 7.
01A6-01B1
0422-0433
LCI configuration
R/W
See table 7.
01B2-01BD
0434-0445
ILK configuration
R/W
See table 7.
01BE-01BF
0446-0447
RESERVED
DHW CONFIGURATION
01C0
0448
DHW enable
R/W
U16
0=DHW disabled,
1=DHW enabled
01C1
0449
DHW demand switch
R/W
U16
Source of DHW demand:
0= Modulation sensor only,
1=EnviraCOM DHW request,
2=DHW switch,
3=Unused,
4=STAT terminal,
5=Reserved,
6=Modbus STAT,
7=Auto: S6 or EnviraCOM DHW request,
8=Auto: S6 or sensor only,
9=Plate heat exchanger
01C2
0450
DHW priority vs CH
R/W
U16
0=CH > DHW,
1=DHW > CH
01C3
0451
DHW priority vs LL
R/W
U16
0=LL > DHW,
1=DHW > LL
01C4
0452
DHW priority time
R/W
U16
0=No DHW priority time,
>0=DHW priority time (seconds)
01C5
0453
DHW setpoint
R/W
U16
-40°-130° (0.1°C precision)
a
01C6
0454
DHW time of day setpoint
R/W
U16
-40°-130° (0.1°C precision)
a
Setpoint when Time Of Day
switch is on.
01C7
0455
DHW on hysteresis
R/W
U16
0°-130° (0.1°C precision)
a
01C8
0456
DHW off hysteresis
R/W
U16
0°-130° (0.1°C precision)
a
01C9
0457
DHW P-gain
R/W
U16
0-1000
01CA
0458
DHW I-gain
R/W
U16
0-1000
01CB
0459
DHW D-gain
R/W
U16
0-1000
01CC
0460
DHW hysteresis step time
R/W
U16
0-64800 seconds (0=Disable hysteresis stepping)
01CD
0461
DHW modulation sensor
R/W
U16
Sensor used for DHW modulation:
0=DHW sensor,
1=Outlet sensor,
2=Inlet sensor,
3=Modbus,
4=Auto: DHW or Inlet sensor,
5=Auto: DHW or Outlet sensor
Summary of Contents for CFC-1000
Page 35: ...Section 2 Installation Part No 750 263 2 21 Figure 2 23 Gas Piping ...
Page 47: ...Section 2 Installation Part No 750 263 2 33 Figure 2 41 Electrical Connection Diagram ...
Page 49: ...Section 2 Installation Part No 750 263 2 35 Figure 2 43 CFC Wiring Diagram dual fuel units ...
Page 50: ...Section 2 Installation 2 36 Part No 750 263 ...
Page 70: ...Section 3 Stack and Intake Vent Sizing and Installation 3 20 Part No 750 263 ...
Page 102: ...Section 4 CFC Commissioning 4 32 Part No 750 263 ...
Page 108: ...Section 5 Service and Maintenance 5 6 Part No 750 263 ...
Page 113: ...Section 6 Parts Part No 750 263 6 5 Figure 6 3 Casing Table 6 5 Casing parts ...
Page 117: ...Section 6 Parts Part No 750 263 6 9 Figure 6 7 Electrical assemblies single fuel ...
Page 123: ...APPENDIX A CB FALCON CONTROLLER ...
Page 124: ......
Page 244: ...CB FALCON 750 265 120 ...
Page 245: ...APPENDIX B CB FALCON PLUG IN MODULE ...
Page 246: ......
Page 250: ......
Page 251: ...APPENDIX C GAS VALVE ...
Page 252: ......
Page 269: ...APPENDIX D CB FALCON MODBUS COMMUNICATION ...
Page 270: ......