Section 4 — CFC Commissioning
4-14
Part No. 750-263
*Access Levels:
Read Only = parameter not configurable
OEM = manufacturer only
Service = password required (default password is 9220)
User = no password required
Lead Lag Configuration
Lead Lag add stage
detection time 1
Service
60
300
seconds
0716
Lead Lag Configuration
Lead Lag add stage error
threshold
Service
5
°F
0718
Lead Lag Configuration
Lead Lag add stage rate
offset
Service
-100
20%
100
%
0719
Lead Lag Configuration
Lead Lag add stage
interstage delay
Service
180
900
seconds
0722
Lead Lag Configuration
Lead Lag drop stage method
1
Service
Firing rate threshold
0723
Lead Lag Configuration
Lead Lag drop stage
detection time 1
Service
60
300
seconds
0725
Lead Lag Configuration
Lead Lag drop stage error
threshold
Service
10
°F
0727
Lead Lag Configuration
Lead Lag drop stage rate
offset
Service
-100
-3%
100
%
0728
Lead Lag Configuration
Lead Lag drop stage
interstage delay
Service
180
900
seconds
0731
Lead Lag Configuration
Lead rotation time
Service
1
24
hours
0733
Lead Lag Configuration
Force lead rotation time
Service
1
168
hours
0734
Lead Lag Configuration
Boiler off options
Service
All Boilers Off option
disabled
0736
Lead Lag Configuration
All boilers off threshold
Service
25
°F
0737
Lead Lag Configuration
Lead Lag CH ODR min.
outdoor temperature
Service
-40
0
140
°F
0518
Lead Lag Configuration
Lead Lag CH ODR low water
temperature
Service
80
180
°F
0519
Lead Lag Configuration
Lead Lag CH ODR maximum
off point
Service
32
194
230
°F
0521
Lead Lag Configuration
Lead Lag CH ODR min.
water temperature
Service
80
230
°F
0527
Lead Lag Configuration
Lead Lag CH outdoor reset
enable
Service
Disabled
0548
Shaded parameters are Safety Parameters and require Verification and manual reset of the control prior to operation. Please refer to Section A, "Changing
parameter settings".
Table 4-1 CFC default parameter settings
Parameter Group
Parameter Name
Access*
Min.
Range
Default Setting
Max.
Range
Parameter
Units
Installation Setting
Modbus
Register
(dec)
Summary of Contents for CFC-1000
Page 35: ...Section 2 Installation Part No 750 263 2 21 Figure 2 23 Gas Piping ...
Page 47: ...Section 2 Installation Part No 750 263 2 33 Figure 2 41 Electrical Connection Diagram ...
Page 49: ...Section 2 Installation Part No 750 263 2 35 Figure 2 43 CFC Wiring Diagram dual fuel units ...
Page 50: ...Section 2 Installation 2 36 Part No 750 263 ...
Page 70: ...Section 3 Stack and Intake Vent Sizing and Installation 3 20 Part No 750 263 ...
Page 102: ...Section 4 CFC Commissioning 4 32 Part No 750 263 ...
Page 108: ...Section 5 Service and Maintenance 5 6 Part No 750 263 ...
Page 113: ...Section 6 Parts Part No 750 263 6 5 Figure 6 3 Casing Table 6 5 Casing parts ...
Page 117: ...Section 6 Parts Part No 750 263 6 9 Figure 6 7 Electrical assemblies single fuel ...
Page 123: ...APPENDIX A CB FALCON CONTROLLER ...
Page 124: ......
Page 244: ...CB FALCON 750 265 120 ...
Page 245: ...APPENDIX B CB FALCON PLUG IN MODULE ...
Page 246: ......
Page 250: ......
Page 251: ...APPENDIX C GAS VALVE ...
Page 252: ......
Page 269: ...APPENDIX D CB FALCON MODBUS COMMUNICATION ...
Page 270: ......