CB FALCON
750-265
28
Fig. 10. Outdoor reset parameters.
Steam Loop Demand and Rate
The CH (Central Heating) Steam Demand and Rate source
compares a selected input sensor to a setpoint.
Burner demand will exist if the sensor pressure falls below the
setpoint minus a hysteresis value. Once the burner demand
signal is on, it remains on until the sensor pressure is above
the setpoint plus a hysteresis value, or until the other selected
demand source input (e.g., Stat, Remote Stat) if any, turns off.
Pump (or output) demand may be driven by the selected
demand source input (Stat input, a remote stat, or by the
sensor alone).
A Proportional-Integral-Differential (PID) controller operates to
generate the demand source’s requested modulation rate.
The Steam Central Heating function is implemented as shown
in Fig. 11.
CH ODR Parameters
LL ODR Parameters
Setpoint
TOD Setpoint
Minimum Outdoor Temp
Maximum Outdoor Temp
Minimum Water Temp
Boost Time
Boost step
Boost recovery step time
Boost Max Setpoint
Setpoint
TOD Setpoint
Minimum Outdoor Temp
Maximum Outdoor Temp
Minimum Water Temp
Boost Time
Boost step
Boost recovery step time
Boost Max Setpoint
M31114
Summary of Contents for CFC-1000
Page 35: ...Section 2 Installation Part No 750 263 2 21 Figure 2 23 Gas Piping ...
Page 47: ...Section 2 Installation Part No 750 263 2 33 Figure 2 41 Electrical Connection Diagram ...
Page 49: ...Section 2 Installation Part No 750 263 2 35 Figure 2 43 CFC Wiring Diagram dual fuel units ...
Page 50: ...Section 2 Installation 2 36 Part No 750 263 ...
Page 70: ...Section 3 Stack and Intake Vent Sizing and Installation 3 20 Part No 750 263 ...
Page 102: ...Section 4 CFC Commissioning 4 32 Part No 750 263 ...
Page 108: ...Section 5 Service and Maintenance 5 6 Part No 750 263 ...
Page 113: ...Section 6 Parts Part No 750 263 6 5 Figure 6 3 Casing Table 6 5 Casing parts ...
Page 117: ...Section 6 Parts Part No 750 263 6 9 Figure 6 7 Electrical assemblies single fuel ...
Page 123: ...APPENDIX A CB FALCON CONTROLLER ...
Page 124: ......
Page 244: ...CB FALCON 750 265 120 ...
Page 245: ...APPENDIX B CB FALCON PLUG IN MODULE ...
Page 246: ......
Page 250: ......
Page 251: ...APPENDIX C GAS VALVE ...
Page 252: ......
Page 269: ...APPENDIX D CB FALCON MODBUS COMMUNICATION ...
Page 270: ......