Fan Configuration
Fan speed up ramp
Service
0
0
1000
RPM/sec
0260
Fan Configuration
Fan speed down ramp
Service
0
0
1000
RPM/sec
0261
Fan Configuration
Fan gain up
Service
0
30
100
0262
Fan Configuration
Fan gain down
Service
0
30
100
0263
Fan Configuration
Fan min. duty cycle
Service
5
10
100
%
0264
High Limits
Outlet high limit enable
Read Only
Enabled
0484
High Limits
Outlet high limit setpoint
Service
32
180
210
°F
0464
High Limits
Outlet high limit response
Read Only
Lockout
0465
High Limits
DHW high limit enable
Service
Disabled
0474
High Limits
DHW high limit setpoint
Service
32
No value
210
°F
0475
High Limits
DHW high limit response
Service
Recycle & hold
0476
Stack Limit
Stack limit enable
Service
Disabled
0466
Stack Limit
Stack limit setpoint
Service
32
250
266
°F
0467
Stack Limit
Stack limit response
Service
Lockout
0468
Stack Limit
Stack limit delay
Service
0
300
900
seconds
0469
Delta T Limits
Delta-T enable - Inlet to
outlet flow
Service
Enabled
Δ
T and
inversion detect
0470
Delta T Limits
Delta-T degrees - Inlet to
outlet flow
Service
14
50
160
°F
0471
Delta T Limits
Delta-T response
Service
Recycle & Delay w/
retry limit
0472
Delta T Limits
Delta-T delay
Service
0
5
480
minutes
0473
Delta T Limits
Delta-T retry limit
Service
0
3
100
retries (b4
lockout)
0485
Delta T Limits
Delta-T rate limit enable
Service
Enabled
0486
Delta T Limits
Delta-T inverse limit time
Service
5
30
minutes
0487
Delta T Limits
Delta-T inverse limit
response
Service
Recycle & Delay w/
retry limit
0488
Delta T Limits
Delta-T enable - Exchanger
to outlet flow
Service
Disabled
0489
Delta T Limits
Delta-T degrees - Exchanger
to outlet flow
Service
14
50
160
°F
0490
Delta T Limits
Delta-T enable - Inlet to
Exchanger flow
Service
Disabled
0494
Delta T Limits
Delta-T degrees - Inlet to
Exchanger flow
Service
14
50
160
°F
0495
T-rise Limit
Outlet T-rise enable
Service
Disabled
not used
0481
T-rise Limit
T-rise degrees
Service
10
°F
not used
0482
T-rise Limit
T-rise delay
Service
5
minutes
notused
0483
T-rise Limit
Exchanger T-rise enable
Service
Disabled
not used
0491
T-rise Limit
T-rise response
Service
Recycle & Delay w/
retry limit
notused
0492
T-rise Limit
T-rise retry limit
Service
10
not used
0493
Heat Exchanger High Limit
Heat exchanger high limit
enable
Service
Disabled
not used
0592
Heat Exchanger High Limit
Heat exchanger high limit
setpoint
Service
32
200
266
°F
not used
0593
Heat Exchanger High Limit
Heat exchanger high limit
response
Service
Recycle & Delay w/
retry limit
notused
0594
Heat Exchanger High Limit
Heat exchanger high limit
delay
Service
0
5
900
minutes
not used
0595
Heat Exchanger High Limit
Heat exchanger retry limit
Service
Lockout
not used
0596
Plate HX Preheat
Plate preheat delay after tap
Service
90
seconds
not used
0688
Plate HX Preheat
Plate preheat setpoint
Service
200
°F
not used
0689
Plate HX Preheat
Plate preheat on recognition
time
Service
10
seconds
not used
0690
Plate HX Preheat
Plate preheat ON hysteresis
Service
5
°F
not used
0691
Table 4-1 CFC default parameter settings
Parameter Group
Parameter Name
Access*
Min.
Range
Default Setting
Max.
Range
Parameter
Units
Installation Setting
Modbus
Register
(dec)
Summary of Contents for CFC-1000
Page 35: ...Section 2 Installation Part No 750 263 2 21 Figure 2 23 Gas Piping ...
Page 47: ...Section 2 Installation Part No 750 263 2 33 Figure 2 41 Electrical Connection Diagram ...
Page 49: ...Section 2 Installation Part No 750 263 2 35 Figure 2 43 CFC Wiring Diagram dual fuel units ...
Page 50: ...Section 2 Installation 2 36 Part No 750 263 ...
Page 70: ...Section 3 Stack and Intake Vent Sizing and Installation 3 20 Part No 750 263 ...
Page 102: ...Section 4 CFC Commissioning 4 32 Part No 750 263 ...
Page 108: ...Section 5 Service and Maintenance 5 6 Part No 750 263 ...
Page 113: ...Section 6 Parts Part No 750 263 6 5 Figure 6 3 Casing Table 6 5 Casing parts ...
Page 117: ...Section 6 Parts Part No 750 263 6 9 Figure 6 7 Electrical assemblies single fuel ...
Page 123: ...APPENDIX A CB FALCON CONTROLLER ...
Page 124: ......
Page 244: ...CB FALCON 750 265 120 ...
Page 245: ...APPENDIX B CB FALCON PLUG IN MODULE ...
Page 246: ......
Page 250: ......
Page 251: ...APPENDIX C GAS VALVE ...
Page 252: ......
Page 269: ...APPENDIX D CB FALCON MODBUS COMMUNICATION ...
Page 270: ......