CB FALCON
101
750-265
CH P gain
Read Only
50
400
CH I gain
Read Only
50
400
CH D gain
Read Only
0
400
CH hysteresis step time
Read Only
1m 0s
mmm:ss
Ignition source
Read Only
A:Internal ignition
(spark)
BLR HSI function
Read Only
A:Blower motor
Igniter on during
Read Only
A:On throughout
PFEP
Pilot type
Read Only
A:Interrupted (off
during Run)
Flame sensor type
Read Only
A:No flame sensor
Purge rate proving
Read Only
B:Prove via HFS
terminal
Lightoff rate proving
Read Only
B:Prove via LFS
terminal
Prepurge time
Read Only
0m 30s
mmm:ss
Preignition time
Read Only
0m 0s
mmm:ss
PFEP
Read Only
C:10 seconds
MFEP
Read Only
C:10 seconds
Run stabilization time
Read Only
0m 10s
mmm:ss
Postpurge time
Read Only
0m 15s
mmm:ss
Interlock start check enable
Read Only
Disabled
Interlock open response
Read Only
A:Lockout
Ignite failure response
Read Only
A:Lockout
Ignite failure retries
Read Only
A:Number of
retries not set
Ignite failure delay
Read Only
5m 0s
mmm:ss
MFEP flame failure response Read Only
A:Lockout
Run flame failure response
Read Only
A:Lockout
Pilot test hold
Hidden
Disabled
NTC sensor type
Read Only
A:10K dual safety
Interrupted air switch enable Read Only
A:no IAS
IAS start check enable
Hidden
Enabled
LCI enable
Read Only
Enabled
PII enable
Read Only
Enabled
Flame threshold
Read Only
2
8
140
.1 Volts/uA
Absolute max fan speed
Read Only
500
5000
7000
RPM
Absolute min fan speed
Read Only
500
800
5000
RPM
PWM frequency
Read Only
D:3000 Hz
Pulses per revolution
Read Only
1
3
10
Fan speed up ramp
Read Only
0
RPM/sec
Fan slow down ramp
Read Only
0
RPM/sec
Fan gain up
Read Only
50
100
Fan gain down
Read Only
50
100
Table 48. Example of a Completed Device Parameter Worksheet. (Continued)
Parameter Name
Customer
Choice - Hidden,
Read Only or
Password
protected
Minimum Range
Default Setting
Maximum Range Parameter Units
Summary of Contents for CFC-1000
Page 35: ...Section 2 Installation Part No 750 263 2 21 Figure 2 23 Gas Piping ...
Page 47: ...Section 2 Installation Part No 750 263 2 33 Figure 2 41 Electrical Connection Diagram ...
Page 49: ...Section 2 Installation Part No 750 263 2 35 Figure 2 43 CFC Wiring Diagram dual fuel units ...
Page 50: ...Section 2 Installation 2 36 Part No 750 263 ...
Page 70: ...Section 3 Stack and Intake Vent Sizing and Installation 3 20 Part No 750 263 ...
Page 102: ...Section 4 CFC Commissioning 4 32 Part No 750 263 ...
Page 108: ...Section 5 Service and Maintenance 5 6 Part No 750 263 ...
Page 113: ...Section 6 Parts Part No 750 263 6 5 Figure 6 3 Casing Table 6 5 Casing parts ...
Page 117: ...Section 6 Parts Part No 750 263 6 9 Figure 6 7 Electrical assemblies single fuel ...
Page 123: ...APPENDIX A CB FALCON CONTROLLER ...
Page 124: ......
Page 244: ...CB FALCON 750 265 120 ...
Page 245: ...APPENDIX B CB FALCON PLUG IN MODULE ...
Page 246: ......
Page 250: ......
Page 251: ...APPENDIX C GAS VALVE ...
Page 252: ......
Page 269: ...APPENDIX D CB FALCON MODBUS COMMUNICATION ...
Page 270: ......