Section 3 — Stack and Intake Vent Sizing and Installation
3-12
Part No. 750-263
G. VENTING FOR MULTIPLE UNITS
Cleaver-Brooks recommends that each Model CFC in a multiple
boiler installation be vented individually. If it becomes necessary to
connect multiple boilers to a common breeching, measures should
be taken to ensure an unrestricted flow of flue gas from each boiler.
An active draft inducer is recommended when venting multiple
boilers. In the absence of a draft inducer, ductwork sizing and
connections require special attention.
Use ‘wye’ connections (not ‘tees’) to connect each boiler to the
common breeching (see Examples 1 and 2 below).
B r e e c h i n g s h o u l d b e s i z e d u p w a r d w h e n n e c e s s a r y t o
accommodate additional boilers (see Example 3). As a rule of
thumb, the cross-sectional area of any ductwork downstream of a
wye connection should be equal to or greater than the combined
area of the incoming vent sections.
When multiple boilers are connected in a CB Falcon-controlled lead/
lag network, a ‘Fan rate during off cycle’ feature is available. When
a boiler goes off line and completes a post purge, the fan will
continue to run at a user-selectable rate. This feature provides a
further measure to prevent flue gas from flowing back into the boiler.
EXAMPLE 1
45
o
6”
10”
14”
6”
6”
6”
GOOD
BAD
Summary of Contents for CFC-1000
Page 35: ...Section 2 Installation Part No 750 263 2 21 Figure 2 23 Gas Piping ...
Page 47: ...Section 2 Installation Part No 750 263 2 33 Figure 2 41 Electrical Connection Diagram ...
Page 49: ...Section 2 Installation Part No 750 263 2 35 Figure 2 43 CFC Wiring Diagram dual fuel units ...
Page 50: ...Section 2 Installation 2 36 Part No 750 263 ...
Page 70: ...Section 3 Stack and Intake Vent Sizing and Installation 3 20 Part No 750 263 ...
Page 102: ...Section 4 CFC Commissioning 4 32 Part No 750 263 ...
Page 108: ...Section 5 Service and Maintenance 5 6 Part No 750 263 ...
Page 113: ...Section 6 Parts Part No 750 263 6 5 Figure 6 3 Casing Table 6 5 Casing parts ...
Page 117: ...Section 6 Parts Part No 750 263 6 9 Figure 6 7 Electrical assemblies single fuel ...
Page 123: ...APPENDIX A CB FALCON CONTROLLER ...
Page 124: ......
Page 244: ...CB FALCON 750 265 120 ...
Page 245: ...APPENDIX B CB FALCON PLUG IN MODULE ...
Page 246: ......
Page 250: ......
Page 251: ...APPENDIX C GAS VALVE ...
Page 252: ......
Page 269: ...APPENDIX D CB FALCON MODBUS COMMUNICATION ...
Page 270: ......